I56-2289-005R

Blinks output by Yellow LED and Remote Trouble Output
once the device has passed a local remote test:

Percent The Detector Has Drifted

Number Of Blinks Output

<10%

None

<20%

1

<30%

2

<40%

3

<50%

4

<60%

5

<70%

6

<80%

7

<90%

8

<100%

9

Modes

*Red

See Note

Below

Yellow and

Remote Trouble

Output

*Green

See Note

Below

Remote

Alarm

Output

Dual Digital Display

Initiating means

Comments & Troubleshooting

Tips

Normal

Off

Off

Blink

Blink

Off

Successful completion

of initialization or

detector reset

Alignment

Off

On

Blink

Blink

On, Relative amount

of signal 0-99, or – if

automatic gain resetting,

or Lo if signal is too low

Alignment Switch

Alarm

On

Off

Off

On

Off

Smoke, Test Filter,

RTS451 or RTS151

Test Stations

Trouble-Drift

Comp Elevated

Signal

Off

3 Quick Blinks

Blink

Blink

Off

Long Term Drift

Reference Out of

Range

• Sunlight into detector or reflector.

• Re-Align detector.

Trouble-Drift

Comp Reduced

Signal

Off

2 Quick Blinks

Blink

Blink

Off

Long Term Drift

Reference Out of

Range

• Clean detector and reflector.

Trouble-Signal

Over Range

Off

2 Quick Blinks

Blink

Blink

Off

Increase of Reflected

Signal

• Inspect line of sight between

detector and reflector for

reflective objects in the pathway.

Trouble-Beam

Blockage

Response

Off

4 Quick Blinks

Blink

Blink

Off

Beam Blockage

• Remove blockage.

• Faulty unit.

Initialization-

Power on

Off

Blink until

complete

Blink

Blink

Off

Apply Power from

discharged state.

Initialization-

alignment exit

Off

Blink until

complete

Blink

Blink

Off

Depressing RESET

switch after alignment

Local Test

(BEAM-200S)

Pass Result

On

Blinks out amount

of drift used

Off

On

Off

Panel or RTS451/KEY

or RTS151/KEY

Remains in alarm until reset or

time-out

Local Test

(BEAM-200S)

Fail Result

Off

On until reset or

time-out

Blink

Blink

Off

Panel or RTS451/KEY

or RTS151/KEY test

input

Remains in fault until reset or

time-out

Local Test

(BEAM-200)

Fail

Off

On until reset or

time-out

Blink

Blink

Off

Panel or RTS451/KEY

or RTS151/KEY test

input

Remains in fault until reset or

time-out

Local Test

(BEAM-200)

Pass Result

On

Blinks out amount

of drift used

Off

On

Off

Panel or RTS451/KEY

or RTS151/KEY

Remains in alarm until reset or

time-out

Note: Green and Red LEDs are controlled by the control panel.

APPENDIx I. OPERATION MODES AND TROUBLEShOOTINg gUIDE: