fIgURE 6. wIRINg CONNECTIONS AT DETECTOR:

SLC (–

)

SLC (+)

SLC (–

)

SLC (+)

RESET

I NPUT

TEST

INPU

T

AUX (–)

REMOTE

ALARM OUT

NOT

USED

REMOTE

TROUBLE OUT

TEST

OPTION (–)

TEST

OPTION (+)

T3

T2

T1

C0260-01

fIgURE 7. wIRINg DIAgRAM:

+ –

+ –

+

+

TO NEXT

DEVICE

FROM

PANEL OR

PREVIOUS

DEVICE

LISTED

REMOTE

POWER

SOURCE

ONLY USED FOR

BEAM200S. SEE

ELECTRICAL

RATINGS.

COMMUNICATION LINE

32 VDC MAX.

TWISTED PAIR IS

RECOMMENDED.

+

T3

T2

T1

C0261-00

fIgURE 8. wIRINg DIAgRAM (RTS451 OR RTS151):

RTS451/KEY

or RTS151/KEY

DETECTOR

PIN 1

REMOTE ALARM OUT

T2-1
T2-2
T2-4

T2-3

AUX (–)

SLC IN +

T1-1
T1-2

T1-3
T1-4

SLC IN –

SLC OUT +
SLC OUT –

RESET INPUT

TEST INPUT

T3-3 REMOTE TROUBLE OUTPUT

OPTIONAL YELLOW LED

PIN 2

PIN 4

PIN 3

PIN 5

C0328-03

fIgURE 9. wIRINg DIAgRAM (RTS451 OR RTS151):

BEAM200/S

ALARM

SIGNAL

CIRCUIT

(NOTE 1)

T2-1

T2-2

NOTE 1: SEE ELECTRICAL RATINGS SECTION OF

THIS MANUAL FOR CIRCUIT OUTPUT RATINGS.

SLC (+)

SLC (–)

RED

C0320-00

INSTALLATION / ALIgNMENT
Reference Figures 10 through 14 for installation, alignment, and maintenance.

The alignment of the BEAM200/BEAM200S is divided into four steps: coarse
alignment, fine adjustment, final gain adjustment, and final verification. It is
necessary for all four steps to be executed properly to ensure proper alignment
of the product. If the detector and reflector are mounted per Mounting Loca-
tions and Mounting Instructions sections of this manual and the alignment
procedures are executed properly, false alarms and nuisance trouble signals
will be minimized.
PRE-ALIgNMENT ChECkLIST

Ensure that both the detector and reflector are mounted securely to

stable surfaces.
Ensure that all wiring is correct.

Ensure that terminal blocks are fully seated into their receptacles on

the detector.
Complete any wiring dressing to minimize movement to the detector

once the alignment procedure is completed.
Ensure that the appropriate number of reflectors are used for the in-

stalled distance. Distances between 230 & 328 Feet (70 - 100m) require
additional reflectors (4 total). The BEAMLRK accessory should be used
in these cases.
Ensure that the line of sight between the detector and reflector is clear

and that reflective objects are not too near. See Mounting Instructions
for more details.
Ensure that both the detector and reflector are mounted within their

operational parameters for off axis angles. See Mounting Instructions
for more details.
Disable the zone or system to prevent unwanted alarms before applying

power.
Ensure power to the detector is “ON”.

Ensure that the appropriate address is set on the code wheels.

You are now ready to begin the alignment procedure.