If the detector fails this test several steps should be taken to determine if the
detector is faulty or simply needs to be re-adjusted before returning the unit.
These steps include:

1. Verify all wiring connections and appropriate power is applied to

the detector.

2. Verify that the optical line of sight is free from obstructions and re-

flective objects.

3. Apply the maintenance procedure in this manual. Repeat the test pro-

cedure. If the detector still fails the test procedure proceed with step 4.

4. Repeat the alignment procedure in this manual. If the alignment pro-

cedure is successful repeat the test procedure. If the detector still fails
the test it should be returned for repair.

NOTE: For the BEAM200S, the external power supply must be con-
nected for the test switch to work.

MAINTENANCE
NOTE:
Before cleaning the detector, notify the proper authorities that the
smoke detector system is undergoing maintenance, and therefore the system
will be temporarily out of service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.

1. Carefully clean the outer housing lens face. A damp soft cloth with a

mild soap may be used. Avoid products with solvents or ammonia.

2. Carefully clean the reflector. A damp soft cloth with a mild soap may be

used. Avoid products with solvents or ammonia.

3. Notify the proper authorities that the system is back on line.
PAINTINg
The outer aesthetic ring may be painted using a spray or brush type paint of
appropriate type. See specification section of this manual for paint types.

NOTE: Never paint the flat lens surface of the outer housing.
SPECIAL NOTE REgARDINg SMOkE DETECTOR gUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.