System Sensor DH100LP User Manual

Page 6

Advertising
background image

D200-15-00

6

I56-0083-009R

DETECTOR

BOARD

7

6

4

(+) IN

(+) OUT

(+)

(+)

5

8

(–)

(–) IN

(–) OUT

1ST DETECTOR

IN LOOP DH100LP

(–)

RA400Z (OPTIONAL)

REMOTE ALARM LED

2.8 VDC NOM.

IN ALARM

DETECTOR

BOARD

7

6

4

(+) IN

(+) OUT

(+)

(+)

5

8

(–)

(–) IN

(–) OUT

LAST DETECTOR

IN LOOP DH100LP

(–)

RA400Z (OPTIONAL)

REMOTE ALARM LED

2.8 VDC NOM.

IN ALARM

E

O

L

R

STYLE D OPTIONAL WIRING

UL LISTED

COMPATIBLE 2-WIRE

CONTROL PANEL

ALARM

INITIATION

LOOP

(+)

(–)

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

1

2

3

4

5

6

3

4

5

Test +

Test / Reset –

Reset +

Test

Reset

RA +

RA –

V Out +

DH100LP

RTS451/RTS451 KEY

6

2

1

Alarm

LED

No Connection

Figure 9. Wiring diagram for the DH100LP to RTS451/RTS451KEY:

Figure 8. System wiring diagram for 2-wire duct smoke detectors (detectors powered from initiating circuit):

H0386-01

Figure 7. Procedure for verifying air flow:

[6.1.5] Filter Replacement
The filters do not substantially affect smoke performance
even when up to 90% of the filter is clogged. Quarterly
visual inspection usually suffices to determine whether the
filters should be replaced because only a high percentage
of contamination affects performance. If further testing is
required, compare differential pressure readings with and
without the filters installed. If the difference exceeds 10%
replace the filters. In no case should the pressure differen-
tial fall below 0.0015 inches of water.

[6.2] Standby, Alarm, And Sensitivity Tests
[6.2.1] Standby And Trouble
Standby —

Look for the presence of the flashing green
LED through the transparent housing cover.
The LED should flash approximately every
10 seconds.

Trouble —

If the Green LED does not flash, then the de-
tector lacks power (check wiring, panel, or
power supply), the detector board is missing
(replace), or the unit is defective (return for
replacement).

Test —

The trouble condition can be caused in-
ten-tionally to verify correct operation of
the sys-tem. Remove the detector board
to cause a trouble condition locally and at
the system control panel.

[6.2.2] Alarm Tests
[6.2.2.1] M02-04-00 Magnet Test
1. Place the painted surface of the magnet onto the TEST

locator on the bottom of the housing (Figure 9).

2. The red alarm LEDs on the detector should latch on,

as should any accessories (i.e. RA400Z, RTS451). Verify
system control panel alarm status, and control panel
execution of all intended auxiliary functions (i.e. fan
shutdown, damper control, etc.).

3. The detector must be reset by the system control panel,

the local reset button, or the remote accessory.

H0193-02

DIFFERENTIAL

PRESSURE

TRANSDUCER

MODEL #607-0

HIGH

LOW

TO SAMPLING TUBE

TO EXHAUST TUBE

VOLT METER

FLUKE MODEL 87

OR EQUIVALENT

1000 OHM 5% 1 WATT RESISTOR

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

15 TO 36VDC

SUPPLY

H0163-00