Figure 10. Testing detector alarm:

[6.2.2.2] RTS451/RTS451KEY Remote Test Station
The RTS451/RTS451KEY Remote Test Station facilitates test
of the alarm capability of the duct smoke detector as in-
dicated in the RTS451/RTS451KEY manual. The DH100LP
duct smoke detector can be reset by the RTS451/RTS-
451KEY. If a system control panel is used, the panel itself
may also require testing.
To install the RTS451/RTS451KEY, connect the device as
shown in Figure 9; wire runs must be limited to 25 ohms
or less per interconnecting wire.

[6.2.3] Sensitivity Tests
[6.2.3.1] MOD400 or MOD400R Test
After verification of alarm capability, use the MOD400R test
module with a voltmeter to check detector sensitivity as
indicated in the test module’s manual. The housing cover
must be removed to perform this test.
If test module readings indicate that the detector head is
outside of the acceptable range that is printed on the label
of the detector, the detector requires cleaning per Section
[7] of this manual.
[7] Detector Cleaning Procedures
Notify the proper authorities that the smoke detector sys-
tem is undergoing maintenance, and that the system will
temporarily be out of service. Disable the zone or system
undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department.
[7.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with

new filters. If they are not heavily coated, use a vacuum
cleaner or compressed air nozzle to remove dust, then
reinstall the filters.

D200-15-00

7

I56-0083-009R

[7.2] Photo Detector Boards
1. Remove the screen by gently grasping on each side and

pulling straight off.

2. Lift the photo chamber in the same fashion. Vacuum

the screen and cover. Use clean, compressed air to
loosen and blow out any remaining debris. Replace-
ment screens (S08-39-01) are available.

3. Vacuum photo chamber, then use clean compressed air

to blow area clean.

4. Replace the chamber by pressing it onto the base. Press

the screen into place. It should fit tightly on the chamber.

[8.0] Board Replacement
[8.1] Detector Board Replacement (part no. A5180)
1. Remove the two detector board mounting screws.
2. Pull gently on the board to remove it.
3. To replace the board, align the board mounting fea-

tures, holes, and the interconnect terminals. Push the
board into place.

4. Secure board with the two mounting screws.
[8.2] Power Board replacement (part no. A5061)
1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it.
4. To replace the board, align the board mounting fea-

tures, holes, and the interconnect terminals. Push the
board into place.

5. Secure board with the two mounting screws.
6. Re-connect wiring to terminal block.