[9] Model DH100LP Air Duct Smoke Detector Specifications

Operating Temperature:

+32° to +131° F

0° to +55° C

Storage Temperature:

–22° to +158° F

–30° to +70° C

Humidity:

10% to 93% R.H. non-condensing

Air Velocity:

100 to 4000 ft./min.

0.5 to 20.3 m/sec.

Dimensions:

14.38” L x 5.5” W x 2.75” D

36.5cm L x 14cm W x 7cm D

Weight:

3.25 pounds

1.5 kg

Electrical Ratings — includes base and detector
System Voltage:

12/24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02 µF maximum

Standby Ratings:

8.5 VDC minimum

35 VDC maximum

120 µA maximum

Alarm Ratings:

4.2 VDC minimum at 10mA

6.6 VDC maximum at 130mA

Alarm current must be limited to 130mA or less by the control panel.

If used, the RA400Z remote lamp operates within the specified alarm currents.

Reset Voltage:

2.50 VDC minimum

Reset Time:

0.3 Sec. maximum

Start-up Time:

34.0 Sec. maximum

Three-Year Limited Warranty

System Sensor warrants its enclosed product to be free from defects in

materials and workmanship under normal use and service for a period

of three years from date of manufacture. System Sensor makes no other

express warranty for the enclosed product. No agent, representative,

dealer, or employee of the Company has the authority to increase or alter

the obligations or limitations of this Warranty. The Company’s obliga-

tion of this Warranty shall be limited to the replacement of any part of

the product which is found to be defective in materials or workman-

ship under normal use and service during the three year period com-

mencing with the date of manufacture. After phoning System Sensor’s

toll free number 800-SENSOR2 (736-7672) for a Return Authorization

number, send defective units postage prepaid to: System Sensor, Returns

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.

Please include a note describing the malfunction and suspected cause

of failure. The Company shall not be obligated to replace units which

are found to be defective because of damage, unreasonable use, modi-

fications, or alterations occurring after the date of manufacture. In no

case shall the Company be liable for any consequential or incidental

damages for breach of this or any other Warranty, expressed or implied

whatsoever, even if the loss or damage is caused by the Company’s

negligence or fault. Some states do not allow the exclusion or limita-

tion of incidental or consequential damages, so the above limitation or

exclusion may not apply to you. This Warranty gives you specific legal

rights, and you may also have other rights which vary from state to state.

D200-15-00