System Sensor DH200PL User Manual

System Sensor Equipment

Advertising
background image

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630-377-6495

www.systemsensor.com

D200-38-00

1

I56-1976-004R

Before installing detectors, please thoroughly read the
NEMA Guide for Proper Use of Smoke Detectors in Duct
Applications, which provides detailed information on detec-
tor spacing, placement, zoning, wiring, and special appli-
cations. Copies of this manual are available from NEMA
(National Electrical Manufacturers Association, 2101 L
Street NW, Washington, DC 20037). NFPA Standards 72 and
90A should also be referenced for detailed information.

NOTICE: This manual shall be left with the owner/user of
this equipment.

IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

General Description
An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem is distributed to the entire building. Smoke detectors

Contents of the Duct Smoke Detector Housing Kit
The DH200PL Duct Smoke Detector consists of the following items: (See Figure 1.)
Figure 1. Exploded View Of Duct Smoke Detector Components:

NOTE: For ducts over 1

1

2

feet (0.46m), longer sampling tubes must be ordered to complete the installation. They must

be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine
the sampling tube required for different duct widths.

1. Complete duct smoke detector assem-

bly with sensor

2. Two #10 x 1

1

4

″ sheet metal mounting

screws

3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws

for the sampling tube and optional

exhaust tube extension

8. One sampling tube end cap
9. One plastic sampling tube
10. One #8 self-tapping screw for plastic

sampling tube

NOTE: A detector sensor board DOES
NOT need to be ordered separately.

Contents Of The Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

designed for use in air duct systems are used to sense the
presence of smoke in the duct.

The DH200PL air duct smoke detector is a photoelectric
detector. This smoke detection method combines with an
efficient housing design that samples air passing through a
duct and allows detection of a developing hazardous condi-
tion. When sufficient smoke is sensed, an alarm signal is
initiated at the fire control panel monitoring the detector,
and appropriate action can be taken to shut off fans, blow-
ers and change over air handling systems, etc. This can
prevent the distribution or it can isolate toxic smoke and
fire gases throughout the areas served by the duct system.

Two LEDs on each detector may illuminate, if programmed
by the system control panel, to provide a local alarm indi-
cation. There is also a remote alarm output for use with
auxiliary devices. The DH200PL has remote test capability
with the RTS451/RTS451KEY Remote Test Station.

DH200PL Intelligent Air Duct Smoke Detector

with Extended Air Speed Range

FOAM

GASKETS

PLASTIC

SAMPLING TUBE

SAMPLING TUBE

FILTERS

PLASTIC SAMPLING TUBE

SELF-TAPPING SCREW

DETECTOR

COVER

DETECTOR BOARD

CONDUIT HOLES

DETECTOR

HOUSING

TERMINAL STRIP

POWER BOARD

COVER MOUNTING

SCREWS

H0456-00