System Sensor DH200PL User Manual

Page 3

Advertising
background image

D200-38-00

3

I56-1976-004R

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

Figure 3. Installation of foam gaskets over sampling
tube bushings:

Figure 5. Tube mounting configurations with varying
air flow direction:

[4.1] Installation For Ducts Greater Than 1

1

2

Feet

(0.46m) But Less Than 8 Feet (2.4m) Wide
1. If the tube is longer than the width of the air duct, drill

a

3

4

″ (19mm) hole in the duct opposite the hole already

cut for the sampling tube. Make sure the hole is 1″ to
2″ (25 to 50mm) below the inlet hole on the opposite
side of the duct to allow moisture drainage away from
the detector. If the tube is shorter than the width of the
air duct,
install the end cap into the sampling tube as
shown in Figure 4. Sampling tubes over 3 ft. (0.91m)
long must be supported at the end opposite the duct
smoke detector.

2. Slide the tube into the housing bushing that meets the

air flow first. Position the tube so that the arrow points
into the air flow, as shown in Figure 4.

3. Secure the tube flange to the housing bushing with two

#6 self-tapping screws.

4. For tubes longer than the width of the air duct, the tube

should extend out of the opposite side of the duct. If there
are more than 2 holes in the section of the tube extend-
ing out of the duct, select a different length using Table
1. Otherwise, trim the end of the tube protruding through
the duct so that 1″ to 2″ (25 to 50mm) of the tube extend
outside the duct. Plug this end with the end cap and tape
closed any holes in the protruding section of the tube. Be
sure to seal the duct where the tube protrudes.

NOTE: The sampling tube end cap is critical to the proper
operation of the duct smoke detectors. The end cap is
needed to create the proper air flow to the sensor of the
duct smoke detector.

Table 1. Sampling tubes recommended for different
duct widths:
Outside Duct Width Sampling Tube Recommended*
1 to 2 ft. (0.3 to 0.6 m)

ST-1.5

2 to 4 ft. (0.6 to 1.2 m)

ST-3

4 to 8 ft. (1.2 to 2.4 m)

ST-5

8 to 12 ft. (2.4 to 3.7 m)

ST-10

*Must extend a minimum of

2⁄3

the duct width

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

H0108-02

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE: Only metal sampling tubes can be installed in

orientations C and D.

[4.2] Installation For Ducts More Than 8 Feet (2.4m) Wide
NOTE:
To install sampling tubes in ducts more than 8 feet

(2.4m) wide, work must be performed inside the
air duct. Sampling of air in ducts wider than 8 feet
(2.4m) is accomplished by using the ST-10 sam-
pling tube. If the tube is shorter than the width of
the air duct, install the end cap into the sampling
tube as shown in Figure 4 and support the end
opposite the duct smoke detector.

Install the sampling tube as follows:
1. Drill a

3

4

-inch (19mm) hole in the duct directly opposite

the hole already drilled for the sampling tube. Make sure
the hole is 1″ to 2″ (25 to 50mm) below the inlet hole on the
opposite side of the duct to allow for moisture drainage.

2. Slide the sampling tube with the flange into the housing

bushing that meets the air flow first. Position the tube so
that the arrow points into the air flow. Secure the tube
flange to the housing bushing with two #6 self-tapping
screws.

H0109-01

H0107-00

Advertising