System Sensor DH200PL User Manual

Page 6

Advertising
background image

D200-38-00

6

I56-1976-004R

for proper operation.

Figure 8. Procedure for verifying air flow:

DIFFERENTIAL

PRESSURE

TRANSMITTER

MODEL #607-01

HIGH

LOW

TO SAMPLING TUBE

TO EXHAUST TUBE

VOLT METER

FLUKE MODEL 87

OR EQUIVALENT

1000 OHM 5% 1 WATT RESISTOR

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

15 TO 36VDC

SUPPLY

H0163-01

[9.1.5] Filter Replacement
The filters do not substantially affect smoke performance
even when up to 90% of the filter is clogged. Quarterly
visual inspection usually suffices to determine whether the
filters should be replaced because only a high percentage
of contamination affects performance. If further testing is
required, compare differential pressure readings with and
without the filters installed. If the difference exceeds 10%
replace the filters. In no case should the pressure differen-
tial fall below 0.0015 inches of water.

[9.2] Standby, Alarm, And Sensitivity Tests
[9.2.1] Standby And Trouble
Standby — If the system control panel is programmed,

look for the presence of the flashing LEDs through

the transparent housing cover. The LED will

flash with each communication.

Trouble — If the detector LEDs do not flash, then the de-

tector lacks power (check wiring, panel pro-

gramming, or power supply), the detector

board is missing (replace), or the unit is defec-

tive (return for repair).

Test —

The trouble condition can be caused intention-

ally to verify correct operation of the system.

Remove the detector board to cause a trouble

condition locally and at the system control

panel.

Figure 9. Wiring Diagram for DH200PL Duct Smoke Detector using a UL listed control panel:

TEST

RA400Z

RT

S451

KEY

COMMON

COM(+

)

COM(–)

TEST

RA400Z

RT

S451

KEY

COMMON

COM(+

)

COM(–)

+

COM

(+)

COM

(–

)

COM (+)

COM

(–

)

COMMUNICATION

LINE

UL LISTED CONTROL

PANEL

1ST DETECTOR

IN LOOP

2ND DETECTOR

IN LOOP

H0105-00

TEST

RA400Z

RTS451 KEY

COMMON

COM(+)

COM(-)

RA400Z

COMMON

DH200PL

RTS451/RTS451KEY

TEST

RTS451 KEY

COM(+)

COM(-)

4

5

6

1

2

3

FIELD INSTALLED

JUMPER

COMMON TEST

LED

RESET

FOR RTS451, TERMINAL 3 IS NOT USED.

(RTS451 DOES NOT HAVE A TERMINAL 6.)

FOR RTS451KEY, TERMINALS 3 AND 6

ARE NOT USED.

TEST

RA400Z

RTS451 KEY

COMMON

COM(+)

COM(-)

RA400Z

COMMON

DH200PL

+

RA400Z

H0458-00

H0457-00

Advertising