System Sensor DH400ACDCI User Manual

Page 11

Advertising
background image

screens (RS24) are available.

3. Vacuum the photo chamber. Use clean compressed air to

blow it clean.

4. Replace the screen by aligning the arrow on top with the

field test port on the detector. Press the screen into
place. It should fit tightly on the chamber.

5. Replace the detector cover and rotate it clockwise to lock

it in place.

[7.3] Ion Heads
1. Remove the detector cover by depressing the three lock

prongs on the top of the cover and rotating the cover
counterclockwise to remove the cover and screen assem-
bly (see Figure 14). The optional CRT400 Cover Removal
Tool makes cover removal easier.

2. Carefully pull the screen out of the cover.
3. Clean the screen thoroughly with a soft brush or

vacuum. Replacement screens (RS14) are available.

4. Brush or vacuum the inside of the cover. The cover may

then be blown out with clean, compressed air.

5. Vacuum the sensing chamber before using clean, com-

pressed air to loosen and blow out any remaining debris.

6. Press the screen back into the cover.
7. Replace the detector cover onto the sensing chamber.

Rotate it clockwise to lock it into place.

REMOVABLE HEAD COVER

CLEANABLE SCREEN

HEAD COVER
REMOVAL SLOT

VANED CHAMBER

TEST SLOT

P/N RS24 (W/O THERMAL)

LOCK PRONG

REMOVABLE SCREEN

(P/N RS14)

REMOVABLE

COVER

FOR

CLEANING

SENSING CHAMBER

Figure 13. Photo head exploded view:

Figure 14. Ion head exploded view:

A78-1213-01

A78-2340-00

[7.4] Reinstallation
1. Reinstall the detector in its housing.
2. Restore system power.
3. Perform Detector Check, Section [5.7].
4. Notify the proper authorities testing has been completed

and the smoke detector system is back in operation.

D400-13-00

11

I56-555-08

Advertising