System Sensor DH400ACDCI User Manual

Page 6

Advertising
background image

24V

120

VAC

220/240

VAC

1

2

12

13

14

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

15

16

17

18

19

20

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS

REMOVED, AND DURING RESET. OPEN CONTACTS

SIGNAL TROUBLE CONDITION TO PANEL.

24V

120

VAC

220/240

VAC

1

2

12

13

14

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

15

16

17

18

19

20

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS

REMOVED, AND DURING RESET. OPEN CONTACTS

SIGNAL TROUBLE CONDITION TO PANEL.

11

10

11

10

8

9

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

8

9

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

ALARM

INITIATION

LOOP

UL LISTED

CONTROL PANEL

FIRST DETECTOR IN THE LOOP

DH400ACDC

LAST DETECTOR IN THE LOOP

DH400ACDC

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR. SEE

SPECIFICATIONS FOR

ADDITIONAL POWER SUPPLY

INFORMATION.

FOR WIRING OF AUXILIARY

DEVICES, REFER TO

MANUFACTURER'S

INSTALLATION INSTRUCTIONS

OR CONTACT MANUFACTURER.

POWER INPUTS ACCEPT

24 VDC, 24 VAC 50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ.

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR.

AUX. CONTACT RATINGS

10A @ 30 VDC

10A @ 250 VAC

500mA MINIMUM @ 24 VDC

NOT INTENDED FOR

CONNECTION TO CONTROL

PANELS.

TROUBLE CONTACT RATING

0.3 A @ 32 VAC/DC

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

Figure 6. System wiring diagram for duct detectors using a UL listed control panel (see Figure 8 for wiring of

optional accessories):

A78-2352-01

D400-13-00

6

I56-555-08