[8] Model DH400ACDC Air Duct Smoke Detector Specifications

Description
HVAC air duct mounted ionization or photoelectronic smoke detector for separately powered systems or stand alone sys-
tems. Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke.

Environmental Limits
Temperature:

32

°

F to 120

°

F

0

°

C to 49

°

C

Humidity:

10% to 93% R.H. non-condensing

Air Velocity:

500 to 4000 Ft/min.
1.5 to 20.3 m/sec.

Test Features
Magnetic test switch, magnetic reset switch, MOD400R test module (optional), RTS451 Remote Test Station (optional).

Mechanical Specifications
Length:

14.5 inches

37 cm

Width:

5 inches

13 cm

Depth (installed):

4 inches

10 cm

Weight:

4 pounds

1.8 kg

Terminals
Captive universal terminal screws with sems plates accept wire sizes of 14 gauge or smaller. The screws can withstand 10
in-lbs of tightening torque without damage.

Accessories
MOD400R

Sensitivity Test Module

RA400Z

Remote Annunciator

RTS451/RTS451KEY

Remote Test Station, test & reset switch with alarm LED

PA400

Piezo Sounder

APA451

Annunciator with piezo, alarm & power LEDs

CRT400

Cover Removal Tool (Ion only)

F36-05-00

Replacement Air Filter (two per package)

M02-04-00

Replacement Test Magnet

P48-21-00

Replacement End Plug for inlet sampling tube

R59-18-00

Replacement Calibrated Test Card (For photo units only)

RS14

Replacement Screen, Ion

RS24

Replacement Screen, Photo

A2650-01

Replacement Installation Kit (mounting hardware)

Sampling (Inlet) Tubes
TUBE

OUTSIDE DUCT WIDTH

ST-1.5

1 to 2 feet

(0.3 to 0.6 m)

ST-3

2 to 4 feet

(0.6 to 1.2 m)

ST-5

4 to 8 feet

(1.2 to 2.4 m)

ST-10

8 to 12 feet

(2.4 to 3.7 m)

Exhaust Tube Extension
A2440-00

5.75 in. (14.6 cm.) additional

D400-13-00

12