[7.3] Ion Heads
1. Remove detector cover by depressing the three lock

prongs on the top of the cover and rotating the cover
counterclockwise to remove the cover and screen assem-
bly. The CRT400 Cover Removal Tool makes cover re-
moval much easier.

2. Carefully pull screen out of cover.
3. Clean screen thoroughly with a soft brush or vacuum.

Replacement screens (RS14) are available.

4. Brush or vacuum inside area of cover. Cover may then

be blown out using clean, compressed air.

5. Vacuum sensing chamber before using clean, com-

pressed air to loosen and blow out any remaining debris.

6. Press screen back into cover.
7. Replace detector cover onto sensing chamber. Turn

clockwise to lock into place.

[7.4] Reinstallation

1.

Reinstall detector in housing.

2.

Restore system power.

3.

Perform Detector Check, Section [5.7] of this manual.

4.

Notify the proper authorities that testing has been com-
pleted and the smoke detector system is operating
again.

REMOVABLE HEAD COVER

CLEANABLE SCREEN

HEAD COVER
REMOVAL SLOT

VANED CHAMBER

TEST SLOT

P/N RS24 (W/O THERMAL)

LOCK PRONG

REMOVABLE SCREEN

(P/N RS14)

REMOVABLE

COVER

FOR

CLEANING

SENSING CHAMBER

Figure 12. Photo head exploded view: