System Sensor DH400P User Manual

Page 12

Advertising
background image

[8] Model Dh400 Air Duct Smoke Detector Specifications

Description
HVAC air duct mounted ionization or photoelectronic smoke detector for 2-wire alarm systems.

Environmental Limits
Temperature:

32

°

to 120

°

F

0

°

to 49

°

C

Humidity:

10% to 93% R.H. non-condensing

Air Velocity:

500 to 4000 ft./min.
1.5 to 20.3 m/sec.

Test Features
Magnetic test switch, MOD400R test module, RTS451 Remote Test Station.

Mechanical Specifications
Length:

14.5 inches

37 cm

Width:

5 inches

13 cm

Depth:(installed)

4 inches

10 cm

Weight:

3.5 pounds

1.6 kg

Terminals
Captive universal terminal screws with sems plates accept wire sizes of 14 gauge or smaller. The screws will withstand 10
in-lbs of tightening torque without damage.

Accessories
M02-04-00

Replacement Test Magnet

RA400Z

Remote Annunciator alarm LED

RTS451/RTS451KEY

Remote Test Station, test switch with alarm and power LEDs

CRT400

Cover Removal Tool (Ion only)

F36-05-00

Replacement Air Filter (two per package)

MOD400R

Sensitivity Test Module

P48-21-00

Replacement End Plug for inlet sampling tube

R59-18-00

Replacement Calibrated Test Card (for Photo units only)

RS14

Replacement Screen, Ion

RS24

Replacement Screen, Photo

A2650-01

Replacement Installation Kit (mounting hardware)

Sampling (Inlet) Tubes
TUBE

OUTSIDE DUCT WIDTH

ST-1.5

1 to 2 feet

(0.3 to 0.6 m)

ST-3

2 to 4 feet

(0.6 to 1.2 m)

ST-5

4 to 8 feet

(1.2 to 2.4 m)

ST-10

8 to 12 feet

(2.4 to 3.7 m)

Exhaust Tube Extension
A2440-00

5.75 in. (14.6 cm.) additional

D400-14-00

12

I56-554-05

Advertising