[2] Figure 1: Exploded View Of Duct Detector Components

SAMPLING TUBE

FILTERS

CONDUIT HOLES

DUCT DETECTOR

HOUSING

TERMINAL STRIP

DUCT DETECTOR

COVER

SAMPLING TUBE

MOUNTING

SCREWS

DETECTOR HEAD

(SUPPLIED SEPARATELY)

EXHAUST

FILTER ADAPTER

DETECTOR BASE

INLET SAMPLING TUBE

(SUPPLIED SEPARATELY)

O-RINGS

FOAM

GASKETS

HOUSING

MOUNTING SCREWS

TEST MAGNET

TUBE

END

PLUG

A78-2093-00

[3] Contents Of The Duct Detector Kit
1. Complete housing base and cover assembly
2. Two #10 sheet metal mounting screws
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two 5/16-inch O-rings
7. Two rubber tube bushing seals
8. Four #6-self tapping mounting screws for the sampling

tube

9. One filter adapter
10.One inlet tube end plug
11.Two #10 speed nuts

NOTE: The inlet sampling tube must be ordered sepa-

rately. It must be the correct length for the width of
the duct where it will be installed. See Table 1 on
page 4 to determine the inlet tube required for dif-
ferent duct widths.

[4] Limitations Of Duct Detectors

WARNING

The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A SUB-
STITUTE FOR OPEN AREA DETECTOR PROTECTION as a
means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.

System Sensor supports this position and strongly recom-
mends that the user read NFPA Standards 90A, 72, and 101.
The DH400 Air Duct Smoke Detectors are listed per UL
268A.

WARNING

This device will not operate without electrical power.
Frequently, fire situations may cause an interruption of
power. The system safeguards should be discussed with
your local fire protection specialist.

WARNING

This device will not sense smoke unless the ventilation sys-
tem is operating.

WARNING

This detector housing is not a weatherproof device, there-
fore it should not be installed above the building roof line
and must be protected from the elements.

[5] Installation Sequence
Step

Page

[5.1] Verify duct air flow direction and velocity

2

[5.2] Drill the mounting holes

3

[5.3] Secure the detector housing to the duct

3

[5.4] Install the sampling tube

3

[5.5] Complete the field wiring

5

[5.6] Install the filters and check pressure differential

8

[5.7] Perform detector check

8

[5.8] Install the cover

8

[5.1] Verify Duct Air Flow Direction And Velocity

Model DH400 detectors are designed to be used in air han-
dling systems having air velocities of 500 to 4000 feet per
minute. Be sure to check engineering specifications to en-
sure that the air velocity in the duct falls within these pa-
rameters. If necessary, an Alnor Model 6000-P velocity
meter or equivalent, may be used to check the air velocity
in the duct.