REV 2 PCI-600 USER’S MANUAL

10

d. From the "Timer Stop" section on the control panel, press the

[→]

key until "DRY

CONTACT" is selected as shown below:

e. Press and hold the

[↓]

key to momentarily turn on the current source:

f. Turn the

[CONTROL KNOB]

clockwise to set the desired current. The screen will be

updated as shown below:

g. Release the

[↓]

key.

h. Press the

[↑]

key to select "ON + TMR" mode and start the test:

i. The PCI-600 will inject the preset current into the bus and turn on the timer. The LCD

will be updated as shown below:

j. The timer will stop and the current source will turn off when the PCI-600 "TIMER STOP"

input detects a change in the relay dry contact, or if the operator presses the

[↓]

key

to select the "OFF" mode.

986mS 59.2CY

Ext I: +0.000 A

Drv I: 20.00 A

0mS 0.0CY

Ext I: -0.000 A
Drv I: 20.00 A