Installation – Lincoln Electric IM10042 RANGER 305 G User Manual

Page 15

Advertising
background image

A-8

INSTALLATION

RANGER® 305G

A-8

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 6 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

40AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE

CONNECTION OF RANGER® 305G TO PREMISES WIRING

WARNING

• Only a licensed, certified, trained electrician should install the machine to a premises or residential

electrical system. Be certain that:

• The installation complies with the National Electrical Code and all other applicable electrical codes.

• The premises is isolated and no feedback into the utility system can occur. Certain state and local

laws require the premises to be isolated before the Generator is linked to the premises. Check your
state and local requirements.

• A double pole, double throw transfer switch in conjunction with the properly rated double throw

circuit breaker is connected between the generator power and the utility meter.