Pumptec 356U SERIES User Manual

Page 4

Advertising
background image

4

Version 061113

Pumptec Operating Instructions and Parts Manual

PUMP SERIES 348U | 350U | 356U

positive displacement pumps providing a specific amount of

fluid constantly while operating. This volume of fluid must

be directed out thru a nozzle or back to a tank because it

cannot be stopped completely without creating excessively

high pressure and risk of damage to pump, components,

property and person. It is recommended a safety device such

as a regulating valve be installed directly on pump head as

protection in case of a failure of another component. Pressure

switches can be used to automate pump operation, but they

must have a pressure regulating device installed as a safety

device.
Fluid can enter a pump either from a filtered tank or

pressurized fluid line.
It is common to use a tank with pumps that are mounted above

the pump. Filtration is important to maintain proper function

of the pump and system. The extent of filtration may be greater

based upon some uses such as misting with ultra-fine nozzles.

iNLEt CONDitiON CHECkLiSt

Inadequate inlet conditions can cause serious malfunctions in

the best designed pump. Surprisingly, the simplest of things

can cause the most severe problems or go unnoticed to the

unfamiliar or untrained eye. REVIEW THIS CHECKlIST bEFORE

OPERATIOn OF AnY SYSTEM. Remember, no two systems are

alike so there can be no OnE best way to setup a system. All

factors must be carefully considered.

iNLEt SUPPLy

should exceed the maximum flow being

delivered by the pump to assure proper performance.

• Open inlet shut-off valve and turn on water supply to avoid

starving the pump. DO nOT RUn PUMP DRY.

• Avoid closed loop systems especially with high temperature,

ultra-high pressure or large flows. Conditions vary with

regulating/unloader valve.

• When using an inlet supply reservoir, size it to provide

adequate liquid to accommodate the maximum output of

the pump, generally a minimum of 6-10 times the gPM

(however, a combination of system factors can change this

requirement).

iNLEt LiNE SizE

should be adequate to avoid starving the

pump
• line size must be a minimum of one size larger than the pump

inlet fitting. Avoid tees, 90-degree elbows or valves in the

inlet line of the pump to reduce the risk of flow restriction

and cavitations.

• The line MUSt be a FlEXIblE hose, nOT a rigid pipe, and

reinforced on SUCTIOn systems to avoid collapsing.

• The simpler the inlet plumbing the less the potential for

problems. Keep the length to a minimum, the number of

elbows and joints to a minimum (ideally no elbows) and the

inlet accessories to a minimum.

• Use pipe sealant to assure airtight, positive sealing pipe

joints.

iNLEt PrESSUrE

should fall within the specifications of

the pump.
• High RPM, high temperatures, low vapor pressures or high

viscosity may increase acceleration loss of liquids.

• Optimum pump performance is obtained with +20 PSI (1.4

bAR) inlet pressure. With adequate inlet plumbing, most

pumps will perform with flooded suction.

• After prolonged storage, pump should be purged of air to

facilitate priming. Disconnect the discharge port to allow

liquid to pass through pump and measure flow.

ByPASS tO iNLEt

– care should be exercised when

deciding the method of bypass from control valves. See Misting

on pages 4 and 5.

• It is recommended that the bypass be directed to a baffled

reservoir tank, with at least one baffle between the bypass

line and the inlet line to the pump.

• Although not recommended, bypass liquid may be returned

to the inlet line of the pump if the system is properly

designed to protect your pump.

• A low-pressure, flexible hose should be used from the bypass

connection to the inlet of the pump.

• Caution should be exercised to avoid undersizing the bypass

hose diameter and length.

• Check the pressure in the bypass line to avoid over-

pressurizing.

USiNg CHEmiCALS

Chemicals can be mixed into the fluid and it is necessary to

understand whether these chemicals will damage the pump or

other system components. Another way to put chemicals into

the fluid is with a downstream injector.
An injector works as a result of the difference of pressure

between the inlet side of injector and discharge side. In most

cases, the pressure on the discharge side cannot exceed 1/2

of the inlet pressure. For example, 1000 PSI into an injector

should allow up to 500-600 PSI spray pressure on discharge

side. There are dual-function nozzles that permit high pressure,

chemical free rinse and low pressure, chemical spray. These

are convenient for the operator and will not harm a properly

designed system.

Advertising
This manual is related to the following products: