APPENDIX A: TROUBLE SHOOTING

If the UPS is not functioning properly, you can refer first to this chapter for simple
troubleshooting before contacting your reseller. This could save you time and
effort but if the problem persist, then consult your service provider.

A.1.1 UPS

The LED and the acoustic signals are a profit tool to individualize immediately
possible problems

Situation

Check Items

Solution

UPS is still in
battery mode
when utility power
is exist. Monitor
display BATTERY
mode, buzzer
emits intermittent
sound.

1. Voltage of utility power is

lower or higher than rated
voltage.

2. Input circuit breaker has

been tripped.

3. Power socket line isn't

connected.

1. Save the computer and

switch off until is normal.

2. Reset circuit breaker
3. Connect power socket line

When utility
power is off,
UPS automatically
power off, buzzer
emits continuous
alarm sound, and
display BATTERY
and UNUSUAL.

1. Overload.
2. Battery is weak.
3. Battery is broken.
4. Battery charging circuit

failure.

1. Reduce load.
2. Charge battery continuous

for 10 hours.

3. Change another battery.
4. Please resort to repair

centre.

When UPS
operate correctly,
overload protector
operate and
lock at once when
add load.

1. Serious overload or short

circuit.

1. Check that watt of load

equipment is huge or short
circuit.

No LEDs display
on the front panel

1.

Contact Atlantis Land.

UPS does not

2. The UPS’s battery is weak 1. Charge the battery.