Connecting the Power Supply

This section describes the precautions for supplying a power voltage.

• If the supplied voltage exceeds the GP unit’s range,

connect a constant voltage transformer.

• For between the line and ground, select a power

supply that is low in noise. If there is an excess amount

of noise, connect a insulating transformer.

• When supplying power to the GP unit, be sure to

separate the input/output and power lines, as shown.

• To increase the noise resistance quality of the power

cord, simply twist each power wire before attaching the

Ring Terminal.

• The power supply cable must not be bundled or

positioned close to main circuit lines (high voltage, high

current), or input/output signal lines.

•The temperature rating of field installed conductors is

60°C.

• DC 24 V input unit must be used with a Class 2

power supply.

• Connect a lightning surge absorber, as shown in the

diagram, to deal with power surges.

• To avoid excess noise, make the power cord as short as

possible.

SEE

Chapter 2 Specifications (page 2-1)

• Use constant voltage and

insulating transformers with
capacities exceeding Power
Consumption value.

• Be sure to ground the surge

absorber (E1) separately from the
GP unit (E2).

• Select a surge absorber that has

a maximum circuit voltage greater
than that of the peak voltage of
the power supply.

GP

GP Power

Input/Output

Power

Main Power

GP

Main Circuit

Lightening Surge

Absorber

GP

E2

FG

E1

Constant

Voltage

Transformer

Twisted-pair cord

GP

FG

I

nsulating

Transformer

T2

T1

Twisted-pair cord

GP

FG

Input/Output

Unit

Main

Power

GP

Power

Input/

Output

Power

Input/Output

Unit

Input/Output

Unit

Operation

Unit