Serial Interfaces
This interface is used to connect an RS-232C/RS-422/RS-485
*1
cable. Connect to the D-SUB 9-pin plug type
connector.
For host controller (PLC, etc.) connection information, refer to the “GP-Pro EX Device/PLC Connection
Manual”.
In the case of RS-232C
In the case of RS-422/RS-485
*1
Communication method is switched via software.
*2
The RI/VCC selection is switched via software. The VCC output is not protected against over current.
To prevent damage or a unit malfunction, use only the rated current.
*3
Select AWG22 cable to use out of two green cables.
Recommended Cable Connector
XM2D-0901 <OMRON Co.>
Recommended Cable Cover
XM2S-0913 <OMRON Co.>
Recommended Jack Screw #4-40 (UNC)
XM2Z-0073 <OMRON Co.>
Cable Color/
Marking Color,
Number
RS-232C
Signal Name
Direction
Description
Brown/White 1
CD
Input
Carrier Detect
Brown/Black 1
RD(RXD)
Input
Receive Data
Brown/White 2
SD(TXD)
Output
Send Data
Brown/White 4
ER(DTR)
Output
Data Terminal Ready
Brown/None
SG
-
Signal Ground
Brown/Black 3
DR(DSR)
Input
Data Set Ready
Brown/Black 2
RS(RTS)
Output
Request to Send
Brown/White 3
CS(CTS)
Input
Send Possible
Brown/Black 4
CI(RI)/VCC
Input/-
Called status display
+5 V
±
5% Output 0.25 A
*2
Green/None
FG
*3
-
Frame Ground (Common with SG)
Cable Color/
Marking Color,
Number
RS-422/RS-485
Signal Name
Direction
Description
Brown/White 1
RDA
Input
Receive Data A(+)
Brown/Black 1
RDB
Input
Receive Data B(-)
Brown/White 2
SDA
Output
Send Data A(+)
Brown/White 4
ERA
Output
Data Terminal Ready A(+)
Brown/None
SG
-
Signal Ground
Brown/Black 3
CSB
Input
Send Possible B(-)
Brown/Black 2
SDB
Output
Send Data B(-)
Brown/White 3
CSA
Input
Send Possible A(+)
Brown/Black 4
ERB
Output
Data Terminal Ready B(-)
Green/None
FG
*3
-
Frame Ground (Common with SG)
• The GP3000H Direct-connect cable’s serial interface is not isolated. When the
host (PLC) unit is also not isolated, and to reduce the risk of damaging the RS-
232C/ RS-422/RS-485 circuit, be sure to connect the SG (Signal Ground)
terminal.