1 serial interfaces, 1 serial interfaces -8 – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 37

Advertising
background image

GP3000H Series Hardware Manual

2-8

2.3.1

Serial Interfaces

This interface is used to connect an RS-232C/RS-422/RS-485

*1

cable. Connect to the D-SUB 9-pin plug type

connector.

For host controller (PLC, etc.) connection information, refer to the “GP-Pro EX Device/PLC Connection

Manual”.

In the case of RS-232C

In the case of RS-422/RS-485

*1

Communication method is switched via software.

*2

The RI/VCC selection is switched via software. The VCC output is not protected against over current.
To prevent damage or a unit malfunction, use only the rated current.

*3

Select AWG22 cable to use out of two green cables.

Recommended Cable Connector

XM2D-0901 <OMRON Co.>

Recommended Cable Cover

XM2S-0913 <OMRON Co.>

Recommended Jack Screw #4-40 (UNC)

XM2Z-0073 <OMRON Co.>

Cable Color/

Marking Color,

Number

RS-232C

Signal Name

Direction

Description

Brown/White 1

CD

Input

Carrier Detect

Brown/Black 1

RD(RXD)

Input

Receive Data

Brown/White 2

SD(TXD)

Output

Send Data

Brown/White 4

ER(DTR)

Output

Data Terminal Ready

Brown/None

SG

-

Signal Ground

Brown/Black 3

DR(DSR)

Input

Data Set Ready

Brown/Black 2

RS(RTS)

Output

Request to Send

Brown/White 3

CS(CTS)

Input

Send Possible

Brown/Black 4

CI(RI)/VCC

Input/-

Called status display

+5 V

±

5% Output 0.25 A

*2

Green/None

FG

*3

-

Frame Ground (Common with SG)

Cable Color/

Marking Color,

Number

RS-422/RS-485

Signal Name

Direction

Description

Brown/White 1

RDA

Input

Receive Data A(+)

Brown/Black 1

RDB

Input

Receive Data B(-)

Brown/White 2

SDA

Output

Send Data A(+)

Brown/White 4

ERA

Output

Data Terminal Ready A(+)

Brown/None

SG

-

Signal Ground

Brown/Black 3

CSB

Input

Send Possible B(-)

Brown/Black 2

SDB

Output

Send Data B(-)

Brown/White 3

CSA

Input

Send Possible A(+)

Brown/Black 4

ERB

Output

Data Terminal Ready B(-)

Green/None

FG

*3

-

Frame Ground (Common with SG)

• The GP3000H Direct-connect cable’s serial interface is not isolated. When the

host (PLC) unit is also not isolated, and to reduce the risk of damaging the RS-

232C/ RS-422/RS-485 circuit, be sure to connect the SG (Signal Ground)

terminal.