2 canopen data transfer settings, 3 canopen cable arrangement – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 10

Advertising
background image

10

13.2 CANopen Data Transfer Settings

CANopen is the networking concept based on the international standard CAN. CANopen is
defined as a uniform application layer by the DS301 specifications of the CiA (CAN in
automation).

13.3 CANopen Cable Arrangement

The CANopen interface uses a DSUB 9-pin plug connector. The plug is assigned with the
CAN_H, CAN_L and CAN_GND connections. CAN_H and CAN_L are two physically
different bus levels. CAN_GND is the common reference potential.

Communication Type

1: N

Connection Method

Bus

Transfer Method

CSMA/NBA. Half-duplex serial transmission.

Transmission Speed/
Communication Distance

No. of Nodes

63 nodes max. Bit variable input: 512 points

*1

, Bit

variable output: 512 points

*1

, Integer variable input: 128

points

*2

, Integer variable output: 128 points

*2

.

*1

When using GP-Pro EX under Ver.2.50, Bit variable enables to input/output 256 points.

*2

When using GP-Pro EX under Ver.2.50, Integer variable enables to input/output 64 points.

Baud rate

*1

*1

Set the baud rate with the software.

Bus length

1000kbps

20m

800kbps

40m

500kbps

100m

250kbps (factory settings)

250m

125kbps

500m

50kbps

1000m

L = Line Termination

Node 1

Node 2

Node n

L

CAN_H

CAN_L

CAN_GND

Twisted Pair Cable

L

Diagram 1

Diagram 2

Advertising