4 canopen communication cable and connectors, 4 canopen communication cable, And other recommended items 11 – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 11: Line termination

Advertising
background image

11

• The cable’s resistance value should be 70m

Ω/m or less.

• The above diagrams use the cable connector “XM2D-0901” by OMRON Co.

„

Line termination

To minimize the signal’s reflections from the end of the cable, a line termination shall be
placed close to both ends of the bus. Connect both ends of the twisted pair cable (CAN_H
and CAN_L) to each LT. Use line termination whose resistance value is 120

Ω. (5%, 1/4W

maximum).

13.4 CANopen Communication Cable and Connectors

• CANopen communication cables and cable connectors are not supplied with the

CANopen Master Unit. Users must prepare cables.

Recommended Cable Connector:

CiA-recommended CANopen (CiA DR-303-1) -
compatible DSUB 9-pin connector (DIN41652) .

CANopen Recommended Transfer Cable:CiA-recommended CANopen (CiA DR-303-1) -

compatible twisted pair cables with shield.

• Please use your own cables or cable connectors with your guarantee.

Termination

Resistance

Shield

D-sub 9 pin (socket)

CANopen Master Unit

CAN-L

Signal

name

2

CAN-H

CAN-GND

FG

Shell

3

7

Pin

D-sub 9 pin (socket)

CAN-L

Signal

name

2

CAN-H

CAN-GND

FG

Shell

3

7

Pin

Shield

Shield

CANopen Master Unit

Diagram 1

Diagram 2