Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 38

Advertising
background image

PLC Ladder Monitor Operation Manual

4-3

„ Error Messages

Error Messages

Solution

There is no CF-Card in the GP.

Please check if the CF Card is inserted properly.

It failed to read a file in the CF-
Card.

• Please check if the CF Card is inserted properly.
• When the ladder program is set as CACHE, it is

possible that a cache does not exist on the CF Card. In
this case, read the ladder program again.

It failed to write a file in the CF-
Card.

• Please check if the CF Card is inserted properly.
• Please check if the CF Card has enough space.
• Check that the “PLCLDMON\MIT_ACPU” or

“PLCLDMON\MIT_ALNK” folders on the CF Card
are not set to “ReadOnly”.

It failed to load the Ladder
Monitor.

• Please check for damage to the CF Card.
• Please format the CF card to either FAT32 or FAT, and

try again.

The Ladder Monitor can’t start
because the Runtime version is
old.

Use the latest version of GP-Pro EX and download the
system to the GP.

The Ladder Monitor can’t start
because the version is old.

Install the latest version of the ladder monitor onto the CF
card.

)

“2.2.2 Setup Procedure” (page 2-4)

There are unsupported
instructions.

This message appears when an instruction is used that is
not supported by the Ladder Monitor. Please check the
version of the programming tool.

The communication error
occurred.

Please check if the connected device and cables are
connected properly. If a password is used in the ladder
program file, please remove that password.