<Compliance and Handling Cautions in Hazardous Locations>

Suitable for use in Class I, Division 2, Groups A, B, C, and D Hazardous Locations only.

WARNING: Explosion hazard - substitution of components may impair suitability for Class I, Division 2.

WARNING: Explosion hazard - do not disconnect equipment while the circuit is live or unless the area is known to be

free of ignitable concentrations.

WARNING: Explosion hazard - When using the PS-A with the AC type power supply, be sure to attach the Power

Switch Cover.

<Control Drawing of USB I/F on PS-A's Front Module>

The information below concerns the use of the USB I/F located on the PS-A unit's front modules used in Class I, Division

2 Groups A, B, C, and D hazardous locations (from Doc No. 35016429).

Notes:

1. Nonincendive Circuit Parameters:

Front USB Port:

Voc = 5.0 V

Isc = 1.25 A

Ca = 10 µF

La = 16 µH

2. Selected Associated Nonincendive Field Wiring Apparatus shall satisfy the following:

3. If the electrical parameters of the cable are unknown, the following values may be used:

Capacitance = 60 pF/ft

Inductive = 0.20 µH/ft

4. Nonincendive Field Wiring must be installed in accordance with article 501.10(B) of the National Electrical Code

ANSI/NFPA 70.

5. Nonincendive Field Wiring Apparatus shall not contain or be connected to another source of power.

SEE

“3.2.3 Attaching the Power Switch cover” (page 3-8)

Nonincendive Field

Wiring Apparatus

-

Front module of

PS-A unit

Voc

Vmax

Isc

lmax

Ca

Ci + C cable

La

Li + L cable

PS-A’s Front module

USB Pin Description
1. Vcc
2. D-
3. D+
4. GND
(See Note 1 for details)
Shield GND

Nonincendive Field

Wiring Apparatus

1 2 3 4

Associated Nonincendive Field Wiring
Apparatus