Wiring

• To avoid an electric shock, when connecting the FP’s power cord terminals to the power ter-

minal block, confirm that the FP’s power supply is completely turned OFF, via a breaker, or
similar unit.

• To avoid the dangers of fire, electric hazards and equipment damage, be sure to use only the

specified voltage when operating the FP.

• Since there is no power switch on the FP unit, be sure to attach a breaker-type switch to its

power cord.

„ Electrical Specification

„ Environmental Specification

„ Power Cord Specifications

Use copper conductors only.

Item

Specification

Pow

e

r Supply

Rated Voltage

AC100V ~ AC240V

Allowable Voltage

AC85V ~ AC264V

Rated Frequency

50 / 60HZ

Allowable Frequency
Range

40Hz - 72Hz

Allowable Voltage Drop

1 cycle (Max.)

(Voltage drop interval must be 1s or more.)

Current Consumption

AC100V 1.1A or less (TYP 0.75A)
AC240V 0.7A or less (TYP 0.44A)

In-Rush Current

60A (Max.)

Voltage Endurance

AC1500V 20mA for 1 minute
(between charging and FG terminals)

Insulation Resistance

DC500V 10M

Ω (Min.)

(between charging and FG terminals)

Item

Specification

Surrounding Air Temperature 0 ~ 50ºC (The panel should not incline more than 30º)

Storage Temperature

-20 ~ +60ºC

Ambient Humidity

10 ~ 90%RH
(No condensation, Wet bulb temperature: 39ºC max.)

Storage Humidity

Air Purity (Dust)

0.1mg/m

3

(Max.) (No electrically conductive dust is

allowed)

Pollution Degree

For use in Pollution Degree 2 environment

Power Cord Diameter

0.75mm

2

to 2.5mm

2

(18AWG to 12 AWG)

Conductor Type

Simple or Twisted Wire

*1

Conductor Length

10mm [0.39 in.]