Watlow EZ-ZONE

®

PM Integrated Controller

34

Chapter 2 Install and Wire

Warning:

Óç

Use National Electric (NEC) or other

country-specific standard wiring and

safety practices when wiring and

connecting this controller to a power

source and to electrical sensors or

peripheral devices. Failure to do so

may result in damage to equipment

and property, and/or injury or loss
of life.

Note:

Maximum wire size termination and

torque rating:

• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination or

two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled

differently, depending on the model

number.

Note:

To prevent damage to the control-

ler, do not connect wires to unused
terminals.

Note:

Maintain electrical isolation between

analog input 1, digital input-outputs,

switched dc/open collector outputs

and process outputs to prevent
ground loops.

Note:

The control output common termi-

nal and the digital common terminal

are referenced to different voltages

and must remain isolated.

Note:

This Equipment is suitable for use in

CLASS I, DIVISION 2, Groups A, B,

C and D or Non-Hazardous locations
only. Temperature Code T4A

Warning:

ç

Explosion Hazard - Dry contact clo-

sure Digital Inputs shall not be used

in Class I Division 2 Hazardous Loca-

tions unless switch used is approved
for this application.

Warning:

ç

Explosion Hazard – Substitution of

component may impair suitability

for CLASS I, DIVISION 2.

Warning:

ç

Explosion Hazard - Do not discon-

nect while the circuit is live or

unless the area is known to be free

of ignitable concentrations of flam-

mable substances.

Quencharc Wiring Example

In this example the Quencharc circuit (Watlow
part# 0804-0147-0000) is used to protect PM
internal circuitry from the counter electro-
magnetic force from the inductive user load
when de-engergized. It is recommended that
this or an equivalent Quencharc be used when
connecting inductive loads to PM outputs.

Quencharc

User Load

N

L_

K_

Standard Bus EIA-485 Communications

T-/R-

common

98
99

CF

CD

CE

B5
D6
D5

Slot C

T+/R+

• Wire T-/R- to the A terminal of

the EIA-485 port.

• Wire T+/R+ to the B terminal of

the EIA-485 port.

• Wire common to the common

terminal of the EIA-485 port.

• Do not route network wires

with power wires. Connect net-

work wires in daisy-chain fash-

ion when connecting multiple

devices in a network.

• Do not connect more than 16

EZ-ZONE PM controllers on a

network.

• Maximum network length:

1,200 meters (4,000 feet)

• 1/8th unit load on EIA-485 bus
PM [4,6,8,9] _ _ _ _ - [*] _ _ _ _ _ _

* All models include Standard Bus

communications (instance 1)

Note:

Do not leave a USB to EIA-485 converter connected to Standard Bus with-

out power (i.e., disconnecting the USB end from the computer while leaving

the converter connected on Standard Bus). Disturbance on the Standard

Bus may occur.

Modbus RTU or Standard Bus EIA-485 Communications

T-/R-

common

98
99

CC

CA
CB

B5

D6
D5

Slot C

T+/R+

• Wire T-/R- to the A terminal of

the EIA-485 port.

• Wire T+/R+ to the B terminal of

the EIA-485 port.

• Wire common to the common

terminal of the EIA-485 port.

• Do not route network wires

with power wires. Connect net-

work wires in daisy-chain fash-

ion when connecting multiple

devices in a network.

• A termination resistor may be

required. Place a 120 Ω resistor

across T+/R+ and T-/R- of last

controller on network.

• Only one protocol per port is

available at a time: either Mod-

bus RTU or Standard Bus.

• Do not connect more than 16

EZ-ZONE controllers on a Stan-

dard Bus network.

• Maximum number of EZ-ZONE

controllers on a Modbus net-

work is 247.

• maximum network length:

1,200 meters (4,000 feet)

• 1/8th unit load on EIA-485 bus.
• Communications instance 1
PM

[4,6,8,9] _ _ _ _ - [1] _ _ _ _

_ _

Note:

Do not leave a USB to EIA-485 converter connected to Standard Bus with-

out power (i.e., disconnecting the USB end from the computer while leaving

the converter connected on Standard Bus). Disturbance on the Standard

Bus may occur.