Watlow EZ-ZONE

®

PM Integrated Controller

83

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`UFA]
[UFA]

Control Loop (1 to 2)

User Failure Action

Select what the control-

ler outputs will do when

the user switches control

to manual mode.

[`oFF]

Off, sets output power

to 0% (62)

[bPLS]

Bumpless Transfer,

maintains same output

power, if it was less than 75%

and stable, otherwise 0% (14)

[MAn]

Fixed Power, sets out-

put power to Manual Power

setting (33)

[USEr]

User, sets output pow-

er to last open-loop set point

the user entered (100)

User

Instance 1

Map 1 Map 2

2182

2662

Instance 2

Map 1 Map 2

2262 2742

0x6B (107)

1 to 2

0xC (12)

- - - -

7012

uint

RWES

[FAiL]
[FAiL]

Control Loop (1 to 2)

Input Error Failure

Select what the control-

ler outputs will do when

an input error switches

control to manual mode.

[`oFF]

Off, sets output power

to 0% (62)

[bPLS]

Bumpless Transfer,

maintains same output

power, if it was less than 75%

and stable, otherwise 0% (14)

[MAn]

Fixed Power, sets out-

put power to Fixed Power

setting (33)

[USEr]

User, sets output pow-

er to last open-loop set point

the user entered (100)

User

Instance 1

Map 1 Map 2

2184

2664

Instance 2

Map 1 Map 2

2264 2744

0x6B (107)

1 to 2

0xD (13)

- - - -

7013

uint

RWES

[MAn]
[MAn]

Control Loop (1 to 2)

Fixed Power

Set the manual output

power level that will take

effect if an input error

failure occurs while User

Failure Action is set to

Manual Fixed.

Set Point Open Loop Limit

Low to Set Point Open Loop

Limit High (Setup Page)

0.0

Instance 1

Map 1 Map 2

2180

2660

Instance 2

Map 1 Map 2

2260 2740

0x6B (107)

1 to 2

0xB (11)

- - - -

7011

float

RWES

[`L;dE]
[ L.dE]

Control Loop (1 to 2)

Open Loop Detect En-

able

Turn on the open-loop

detect feature to monitor

a closed-loop operation

for the appropriate re-

sponse.

[``no]

No (59)

[`YES}

Yes (106)

No

Instance 1

Map 1 Map 2

1922

2402

Instance 2

Map 1 Map 2

1992 2472

0x97 (151)

1 to 2

0x16 (22)

74

8039

uint

RWES

[`L;dt]
[ L.dt]

Control Loop (1 to 2)

Open Loop Detect

Time

The Open Loop Detect

Deviation value must oc-

cur for this time period

to trigger an open-loop

error.

0 to 3,600 seconds

240

Instance 1

Map 1 Map 2

1924

2404

Instance 2

Map 1 Map 2

1994 2474

0x97 (151)

1 to 2

0x17 (23)

75

8040

uint

RWES

[`L;dd]
[ L.dd]

Control Loop (1 to 2)

Open Loop Detect De-

viation

The value entered repre-

sents the Process Value

deviation that must

occur to trigger an open-

loop error.

-1,999.000 to 9,999.000°F or

units

-1,110.555 to 5,555.000°C

10.0°F or

units

6.0°C

Instance 1

Map 1 Map 2

1926

2406

Instance 2

Map 1 Map 2

1996

2476

0x97 (151)

1 to 2

0x18 (24)

76

8041

float

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set