Watlow EZ-ZONE PM Integrated Controller User Manual

Page 89

Advertising
background image

Watlow EZ-ZONE

®

PM Integrated Controller

86

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`o;Ct]
[ o.Ct]

Output Digital (1 to 4)

Output Control

Set the output control

type. This parameter

is only used with PID

control, but can be set

anytime.

[`Ftb]

Fixed Time Base (34)

[`utb]

Variable Time Base

(103)

Fixed

Time

Base

Instance 1

Map 1 Map 2

882

1002

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

1 to 4

2

85

6002

uint

RWES

[`o;tb]
[ o.tb]

Output Digital (1 to 4)

Output Time Base

Set the time base for

fixed-time-base control.

0.1 to 60.0 seconds (solid-state

relay or switched dc)

5.0 to 60.0 seconds (mechani-

cal relay or NO-ARC power

control)

1.0 sec.

for SSR

or swdc

5.0 for

relay

Instance 1

Map 1 Map 2

884

1004

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

1 to 4

3

86

6003

float

RWES

[`o;Lo]
[ o.Lo]

Output Digital (1 to 4)

Output Low Power

Scale

The power output will

never be less than the

value specified and will

represent the value at

which output scaling

begins.

0.0 to 100.0%

0.0%

Instance 1

Map 1 Map 2

896

1016

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

1 to 4

9

87

6009

float

RWES

[`o;hi]
[ o.hi]

Output Digital (1 to 4)

Output High Power

Scale

The power output will

never be greater than

the value specified and

will represent the value

at which output scaling

stops.

0.0 to 100.0%

100.0%

Instance 1

Map 1 Map 2

898

1018

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

1 to 4

0xA (10)

88

6010

float

RWES

[`o;ty]
[ o.ty]

Output Process (1 or 3)

Output Type

Select whether the pro-

cess output will operate

in volts or milliamps.

[uoLt]

Volts (104)

[`MA]

Milliamps (112)

Volts

Instance 1

Map 1 Map 2

720

840

Instance 3

Map 1 Map 2

800

920

0x76 (118)

1 or 3

1

95

18001 uint

RWES

[``Fn]
[ Fn]

Output Process (1 or 3)

Output Function

Set the type of func-

tion that will drive this

output.

[`oFF]

Off (62)

[heat]

Heat (36)

[Cool]

Cool (20)

[dupl]

Duplex (212)

[ALM]

Alarm (6)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

[rmt]

Retransmit (213)

Off

Instance 1

Map 1 Map 2

722

842

Instance 3

Map 1 Map 2

802

922

0x76 (118)

1 or 3

2

96

18002 uint

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set

Advertising