Watlow EZ-ZONE

®

RMC Module

116

Chapter 4 Setup Page

RMC Module • Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[`PRo]
[`Set]
Profile Menu

[R;typ]

[R.tyP]

Profile

Ramping Type

Use to have the ramp-

ing set point change at

a set Rate or over a set

interval of Time as pro-

file steps.

[rate]

Rate (81)

[``ti]

Time (143)

Time

5354

0x7A

(122)

1

0x26 (38)

- - - -

22038

uint

RWE

[P;typ]

[P.tyP]

Profile

Profile Type

Set the profile startup to

be based on a set point

or a process value.

[StPt]

Set Point (85)

[`Pro]

Process (75)

Set Point

5294

0x7A

(122)

1

8

- - - -

22008

uint

RWE

[`GSE]

[ gSE]

Profile

Guaranteed Soak En-

able

Enables the guaranteed

soak deviation function

in profiles.

[`oFF]

Off (62)

[``on]

On (63)

Off

5290

0x7A

(122)

1

6

- - - -

22006

uint
RWE

[GSd1]

[gSd1]

Profile

Guaranteed Soak De-

viation 1

Set the value of the

deviation band that will

be used in all profile

step types. The process

value for control loop 1

must enter the deviation

band before the step can

proceed. .

0.0 to 9,999.000°F or units
0.0 to 5,555.000°C

10.0°F or

units

6.0°C

5292

0x7A

(122)

1

7

- - - -

22007

float
RWE

[GSd2]

[gSd2]

Profile

Guaranteed Soak De-

viation 2

Set the value of the

deviation band that will

be used in all profile

step types. The process

value for control loop 2

must enter the deviation

band before the step can

proceed.

0.0 to 9,999.000°F or units
0.0 to 5,555.000°C

10.0°F or

units

6.0°C

5360

0x7A

(122)

1

0x29 (41)

- - - -

22041

float
RWE

[GSd3]

[gSd3]

Profile

Guaranteed Soak De-

viation 3

Set the value of the

deviation band that will

be used in all profile

step types. The process

value for control loop 3

must enter the deviation

band before the step can

proceed..

0.0 to 9,999.000°F or units
0.0 to 5,555.000°C

10.0°F or

units

6.0°C

5362

0x7A

(122)

1

0x2A (42)

- - - -

22042

float
RWE

Note:

Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S:

User Set