Wiring a Serial EIA-485 Network

Do not route network wires with power wires. Con-

nect network wires in daisy-chain fashion when con-

necting multiple devices in a network. A termina-

tion resistor may be required. Place a 120 Ω resistor

across T+/R+ and T-/R- of the last controller on a

network. Only one protocol per port is available at a

time: either Modbus RTU or Standard Bus.

Note:

Termination resistors when used, require a termina-

tion resistor at both ends of the network.

A Network Using Watlow's Standard Bus and an RUI/Gateway

- A

+ B

com

- A

+ B

common

power

- A

+ B

common

power

power

power

EZ-ZONE PM

EZ-ZONE ST

ST_ _ - (B or F) _ M _ -_ _ _ _

98

99

CF

CD

CE

B5

D6

D5

Power

Supply

fuse

EZ-ZONE RM

98

99

Slot C

power

CZ

CE

CX

CY

CD

CF

- A

+ B

common

98
99

CF
CD
CE
B5
D6
D5

98
99

CF
CD
CE

RUI/Gateway

EZKB-_ A _ _- _ _ _ _

A Network Using Modbus RTU

- A

+ B

com

98
99

CC
CA
CB

B5
D6
D5

power

- A

+ B

common

power

- A

+ B

common

power

power

power

power

EZ-ZONE PM

EZ-ZONE ST

ST_ _ - (B or F) _

M _ -_ _ _ _

PLC

98

99

CC

CA

CB

B5

D6

D5

Power

Supply

fuse

EZ-ZONE RM

98

99

Slot C

power

CZ

CB

CX

CY

CA

CC

- A

+ B

common