Watlow EZ-ZONE

®

RMH Module

111

Chapter 6 Features

to) the Modbus address of a parameter within the

controller.
Assembly Working Addresses
- Fixed addresses directly related to their associ-

ated "Assembly Definition Addresses" (e.g., As-

sembly Working Addresses 200 & 201 will as-

sume the parameter pointed to by Assembly Defi-

nition Addresses 40 & 41).
When the Modbus address of a target parameter is

stored in an "Assembly Definition Address" its cor-

responding working address will return that param-

eter’s actual value. If it’s a writable parameter, writ-

ing to its working register will change the param-

eter’s actual value.

As an example, Modbus register 410 contains the

Analog Input 1 Process Value (See Operations Page,

Analog Input Menu). If the value 410 is loaded into

Assembly Definition Address 91, the process value

sensed by analog input 1 will also be stored in Mod-

bus registers 250 and 251. Note that by default all

registers are set to Hardware ID.

The table (See Appendix:

Modbus Programmable

Memory Blocks

) identified as "Assembly Definition

Addresses and Assembly Working Addresses" reflects

the assemblies and their associated addresses.