Control function, Watlow ez-zone, Rmh module – Watlow EZ-ZONE RMH User Manual

Page 128: Chapter 6 features

Advertising
background image

Watlow EZ-ZONE

®

RMH Module

125

Chapter 6 Features

Control Function

Overview

Instances - 1 - 16 per RMH

Control M

ode

Rem

ote Set P

oint Enable

Rem

ote Set P

oint Enable

Rem

ote Set P

oint

Type

User F

ailure

Action

Loop Error Clear Request

Input Error F

ailure

Fixed P

ow

er

Open Loop D

etect Enable

Open Loop D

etect

Tim

e

Open Loop D

etect D

eviation

Ram

p Action

Ram

p Scale

Ram

p Rate

Profiling Enable

Closed Loop Low

Set P

oint

Set P

oint

Lim

it

Open

Low

Closed Loop H

igh Set P

oint

Set P

oint

Lim

it

Open

High

Heat

Algorithm

Cool

Algorithm

TRU

-TU

NE+ Enable

Autotune

Aggressiveness

Peltier D

ela

y

TRU

-TU

NE+ Band

TRU

-TU

NE+ G

ain

Cool O

utput Curve

Autotune Set P

oint

Autotune

Closed Loop Set P

oint

Idle Set P

oint

Heat Proportional Band

Cool Proportional Band

Heat H

ysteresis

Cool H

ysteresis

Deadband

Open Loop Set P

oint

Cool Power

Heat Power

Control Mode Active

Tune Status

Loop Error

Closed Loop Set Point

Open Loop Set Point

Loop Power

Process Value Active

Source Function A

Source Instance A
Source Zone A

Source Error A

Source Function B

Source Instance B

Source Zone B
Source Error B

Tim

e Integral

Tim

e D

erivative

Control

[SFn;A]

Source Function A : Analog Input, Process Value

[h;Ag]

Heat Algorithm : Off, PID, On/Off

[C;Ag]

Cool Algorithm : Off, PID, On/Off

[t;tUn]

TRU-TUNE+ Enable : No, Yes

[t;bnd]

TRU-TUNE+ Band : 0 to 100

[t;gn]

TRU-TUNE+ Gain : 1 to 6

[t;Agr]

Autotune Aggressiveness : Under, Critical, Over

[r;En]

Remote Set Point Enable : No, Yes

[Si;b]

Source

B (Remote Set Point Source Instance) : 1 to 250

Instance

[S2;b]

Source

B : 0 to 16

Zone

[MAn]

Fixed Power : -100.0 to 100.0 %

[L;dE]

Open Loop Detect Enable : No, Yes

[L;dt]

Open Loop Detect Time : 0 to 3,600 seconds

[rP]

Ramp Action : Off, Startup, Set Point, Both

[r;SC]

Ramp Scale : Hours, Minutes

[C;M]

Control Mode : Off, Auto, Manual

[A;tSP]

Autotune Set Point : 50 to 200 %

[C;SP]

Closed Loop Set Point : -1,999.000 to 9,999.000

[id;S]

Idle Set Point : -1,999.000 to 9,999.000

[h;Pb]

Heat Proportional Band : 0.001 to 9,999.000

[h;hy]

Heat Hysteresis : 0.001 to 9,999.000

[C;Pb]

Cool Proportional Band : 0.001 to 9,999.000

[C;hy]

Cool Hysteresis : 0.001 to 9,999.000

[ti]

Time Integral : 0 to 9,999 seconds

[td]

Time Derivative : 0 to 9,999 seconds

[C;Cr]

Cool Output Curve : Off, Non-linear curve 1,

-

2

Non linear curve

[r;ty]

Remote Set Point Type : Auto, Manual

[SFn;B]

Source Function B (

:

, Analog

Input, Current, Cool Power, Heat Power, Power, Linearization, Math,
Process Value, Set Point Closed, Set Point Open, Variable

Remote Set Point Source) None

[UFA]

User Failure Action : Off,

,

User

Bumpless Transfer Manual Power,

[FAiL]

Input Error Failure :

User

Off, Bumpless Transfer, Manual Power,

[L;SP]

Low Set Point : -1,999.000 to 9,999.000

[h;SP]

High Set Point : -1,999.000 to 9,999.000

[SP;Lo]

Set Point

Limit

: -100.0 to 100.0 %

Open

Low

[SP;hi]

Set Point

Limit

: -100.0 to 100.0 %

Open

High

[L;dd]

Open Loop Detect Deviation : -1,999.000 to 9,999.000

[r;rt]

Ramp Rate : 0.000 to 9,999.000

[db]

Deadband : -1,000.000 to 1,000.000

[o;SP]

Open Loop Set Point : -100.0 to 100.0 %

[iS;A]

Source Instance A : (not changeable)*

[LooP]

Loop Menu

[`SEt]

Setup Page

[P;dL]

Peltier Delay : 0.0 to 5.0

[r;En]

Remote Set Point Enable : No, Yes

[C;M]

Control Mode : Off, Auto, Manual

[A;tSP]

Autotune Set Point : 50 to 200 %

[AUt]

Autotune : No, Yes

[C;SP]

Closed Loop Set Point : -1,999.000 to 9,999.000

[id;S]

Idle Set Point : -1,999.000 to 9,999.000

[h;Pb]

Heat Proportional Band : 0.001 to 9,999.000

[h;hy]

Heat Hysteresis : 0.001 to 9,999.000

[C;Pb]

Cool Proportional Band : 0.001 to 9,999.000

[C;hy]

Cool Hysteresis : 0.001 to 9,999.000

[ti]

Time Integral : 0 to 9,999 seconds

[td]

Time Derivative : 0 to 9,999 seconds

[db]

Deadband : -1,000.000 to 1,000.000

[o;SP]

Open Loop Set Point : -100.0 to 100.0 %

[LooP]

Loop Menu

[oPEr]

Operation Page

[C;MA]

Control Mode Active : Off, Auto, Manual

[h;Pr]

Heat Power : 0.0 to 100.0 %

[C;Pr]

Cool Power : 0.0 to 100.0 %

[C;SP]

Closed Loop Set Point : -1,999.000 to 9,999.000

[Pu;A]

Process Value Active : -1,999.000 to 9,999.000

[Mon]

Monitor Menu

[oPEr]

Operation Page

Loop Power : -100.0 to 100.0 %
Loop Error: None, Open Loop, Reversed Sensor
Loop Error Clear Request : Ignore, Clear
Tune Status : Off, Cross 1 Positive, Cross 1 Negative,

Cross 2 Positive, Cross 2 Negative, Cross

3 Positive, Cross 3 Negative, Measuring

Max, Measuring Min, Calculating, Com-

plete, Timeout

Note:

Control Loop primary source instance must match Pro-
cess Value or Analog Input instance