Process inputs 1 through 16, Digital inputs 1 through 12 – Watlow EZ-ZONE RMH User Manual

Page 29

Advertising
background image

Warning:

ç

Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.

Note:

Maximum wire size termination and

torque rating:
• 0.0507 to 3.30 mm2 (30 to 12 AWG)
single-wire termination or two 1.31
mm2 (16 AWG)
• 0.8 Nm (7.0 in-lb.) torque

Note:

Adjacent terminals may be labeled
differently, depending on the model
number.

Note:

To prevent damage to the controller,
do not connect wires to unused ter-
minals.

Note:

Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs

to prevent ground loops.

Warning:

ç

Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2.

Warning:

ç

Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.

Watlow EZ-ZONE

®

RMH Module

26

Chapter 2 Install and Wire


Suppressor Note:
Switching pilot duty inductive loads
(relay coils, solenoids, etc .) with the
mechanical relay, solid state relay or
open collector output options requires
use of an R .C . suppressor for AC load or
a diode for a DC load .

Process Inputs 1 through 16

RMH Part # Digit 5, 6, 7, 8 is 1

-

+

-

+

-

+

-

+

S_
R_
S_
R_
S_
R_
S_
R_

Slot A, B, D, E

-

+

-

+

-

+

-

+

S_
R_
S_
R_
S_
R_
S_
R_

Slot A, B, D, E

• 0 to 20 mA @ 100 Ω input imped-

ance

• 0 to 10V

Î

(dc) @ 20 kΩ input imped-

ance

• 0 to 50 mV

Î

(dc) @ 20 MΩ input im-

pedance

• scalable

Slot 1:

RMHx-(1)xxx-xxxx

(Inputs 1 to 4)

Slot 2:

RMHx-x(1)xx-xxxx

(Inputs 5 to 8)

Slot 3:

RMHx-xx(1)x-xxxx

(Inputs 9 to 12)

Slot 4:

RMHx-xxx(1)-xxxx

(Inputs 13 to 16)

Digital Inputs 1 through 12

RMH Part # Digit 7, 8 is C

Common

DC Input

B_
D_
D_
D_
D_
D_
D_
Z_

Slot D, E

Supply

DC Input

DC Input

DC Input

DC Input

DC Input

Internal

Digital Input Event

Conditions

• Voltage
- Input inactive when <

2V

- Input active when >

3V

• Dry Contact
- Input inactive when >

100KΩ

- Input active when <

50Ω

• Six user configurable

digital inputs/outputs

per slot

- Slot D DI 1 - 6
RMHx-xx(C) xx-xxxx

- Slot E DI 7 - 12
RMHx-xxx(C)-xxxx

Voltage Input

common

Vdc

D

_

B

_

Dry Contact

24 Vdc

_

Z

_

D

Advertising