Setup-Input

Decimal 2

Select the decimal point location for channel B data. This prompt, in
conjunction with the Range Low and Range High prompts, allows you to
format and limit units of measure for channel B.

• All prompts with units of measure related to channel B will display in the

selected decimal format.

• This affects propbands, alarm set points, process set points, calibration

offsets, deadbands and ranges.

[dEC2] This prompt appears only if [`In2] is set to a process input.

Default

[```)]

[``)0]

[`)00]

[)000]

[dEC2]

[dEC2]

[dEC2]

[dEC2

Range Low 2 and Range High 2

Select the low and high limits for channel B. These prompts limit the
adjustment range for the set points. The default values are the same as
the limits of the sensor you selected by setting the input 2 DIP switch and
selecting a value for Input 2 [`In2].

• Process inputs are scaled by these values. Range high is the value dis-

played when the maximum process signal is present at the input. Range
low is the value displayed when the minimum process signal is present
at the input.

Example: Set [`In2] to [4-20]mA.

Set [`rL2] to [`100].
Set [`rH2] to [`500].
A 4mA input will display [`100].
A 12mA input will display [`300].
A 20mA input will display [`500].

• The low and high values of each sensor type are listed on the specifica-

tions page of the Appendix.

• Choose between Fahrenheit and Celsius at the [`C_F] prompt in the

Global Menu.

[`rL2] [`rH2] These prompts appear only if [`In2] is not set to [``no]

.

[`rH2]

[`rL2]

NOTE:
These values do not
affect the low or the
high set point limit
for process alarms.

[dEC2]

[`rL2]
[`rH2]

Range Low 2 and
Range High 2
continued on next
page.