Series D8 User’s Guide

Chapter 4: Operation and Setup

Doc. 0600-3120-2000

Watlow Anafaze

99

Figure 4.8

Application Using Process
Variable Retransmit

Table 4.8 shows the parameter setup for this example.

Table 4.8

Parameters Settings for Process
Variable Retransmit Example

Menu

Parameter

Value

Comment

PV retrans

Ht output
retrans

PV 1

Choose to retransmit the loop 1 process variable.

PV retrans

Ht retrans
LowPV

0˚F

This is the input value represented by a 0 percent

output signal. The recorder input is a linear 4 to 20

mA signal representing a range of 0° F to 1000° F,

so we will use a 0 percent output signal to represent

0° F.

PV retrans

Ht retrans
HighPV

1000˚F

This is the input value represented by a 100 percent

output signal. The recorder input is a linear 4 to 20

mA signal representing a range of 0° F to 1000° F,

so we will use a 100 percent output signal to repre-

sent 1000° F.

PV retrans

Cl output
retrans

none

Not using the cool output of loop 2 to retransmit a

process variable.

D8

Furnace

Power

Controller

To Data

Logger

Loop 1 PID Output

Loop 2 PID Output

Heater

Loop 1

Input

Process

Variable

Serial

DAC