Figure 2.7—tb50 mounted on din rail (side) 17, Figure 2.8—mounting a tb50 with standoffs 17 – Watlow Series D8 User Manual
Page 35
Series D8 User’s Guide
Chapter 2: Installation
Doc. 0600-3120-2000
Watlow Anafaze
17
To remove the TB50 from the rail, use a flathead screw driver
to unsnap the bracket from the rail. See Figure 2.7.
Figure 2.7
TB50 Mounted on DIN Rail (Side)
Mounting with Standoffs
1. Remove the DIN rail mounting brackets from the TB50.
2. Choose a location with enough clearance to remove the
TB50, its SCSI cable and the controller itself.
3. Mark the four mounting holes.
4. Drill and tap four mounting holes for #6 (3.5 mm) screws
or bolts.
5. Mount the TB50 with four screws or bolts.
There are four smaller holes on the terminal board. Use these
holes to secure wiring to the terminal block with tie wraps.
Figure 2.8
Mounting a TB50 with Standoffs
Removal
Catch for
Screwdriver
DIN Rail
Snap Latch
Hook Side
3.4 in
(86 mm)
3.6 in
(91 mm)
2.6 in
(66 mm)
(18 mm)
0.2 in
(5 mm)
0.2 in
(5 mm)
SCSI Connector
0.2 in
4 Holes for
0.7 in
(5 mm)
#6 (3.5 mm)
Bolts or Screws