How to Set Up Differential Control

Set up differential control as you would set up ratio control.

Set the Control ratio parameter to 1.0, and enter the desired

set point differential (offset) at the Ratio SP diff parameter.

Differential Control Example: Thermoforming

A thermal forming application requires that the outer heaters

operate at temperature 50º F hotter than the center heaters.

The center heaters use infrared (IR) sensors for temperature

feedback. The outer heaters use thermocouples for feedback.
We can use differential control to control the outer heaters at

a 50º F differential to the central heaters. For example, if the

set point for the center heaters is 325º F, the set point of the

outer heaters will be 375º F.
In this application, the center heaters will be controlled by the

master loop (on loop 1), and the outer heaters will be con-

trolled by the ratio loop (on loop 2).
To set up this application, first set up the master loop (loop 1)

for PID control with a set point of 325º F. Then, for the ratio

loop (loop 2), set the parameters in the Ratio menu as shown

in Table 4.12.

Table 4.12

Parameter Settings for the Ratio
Loop (Loop 2) for the Example

To complete the differential control setup, loop 1 and loop 2

must be configured for inputs, outputs and alarms.

Setting Up Remote Analog Set Point

Remote analog set point allows external equipment, such as a

PLC or other control system, to change the set point of a loop.

Menu

Parameter

Value

Comment

Ratio

Ratio master loop

01

Loop 1 is the master loop.

Ratio

Ratio low SP

300.0˚F

The lowest allowable set point for the ratio

loop. For this example, we’ll use 300.0.

Ratio

Ratio high SP

400.0˚F

The highest allowable set point for the ratio

loop. For this example, we’ll use 400.0.

Ratio

Control ratio

1.0

For differential control, always set this parame-

ter to 1.0.

Ratio

Ratio SP diff

50˚F

The set point differential, or offset.