4. WIRING

For working on the electric wire tubes or the flexible
tubes (PF1/2), remove the waterproof gland and attach
them directly to the wiring port.

Gasket

Washer

Tightening gland

When working on conduit pipes or flexible pipes (PF1/2 only)

Cable

PF1/2

F0405.EPS

Figure 4.3.2

Waterproof Gland with Union Joint
(Optional code EU)

Plastic gland

Gasket

F0406.EPS

Figure 4.3.3

Plastic Gland (Optional code EP)

(3) Conduit Wiring

When wiring the conduits, pass the conduit through the
wiring connection port, and utilize the waterproof
gland to prevent water from flowing in. Place the
conduit pipe on an angle as shown in Figure 4.3.4.
Install a drain valve at the low end of the vertical pipe,
and open the valve regularly.

Drain valve

F0407.EPS

Figure 4.3.4

Conduit Wiring

4.4 Wiring Connections

4.4.1

Removing Cover

Loosen cover locking screw 2 clockwise using a
hexagonal wrench (nominal size 3 mm) to unlock the
cover. (Upon shipment from the manufacturing plant,
the cover is unlocked.) Hold the flowmeter with your
hand and remove the cover by turning it in the direc-
tion of the arrow as shown below.

F0408.EPS

Cover locking screws

Figure 4.4.1

Removing the Terminal Box Cover