<5. Configuration>

5-15

IM 01C50T02-01E

PV_FTIME

Stipulates the time constant (in seconds) of the

first-order lag filter inside the AI block.

OUT_SCALE

Stipulates the range of OUT (by setting the

upper and lower range limits). The unit can also

be set freely. OUT_SCALE is set to 0 to 100%

before the YTA320 is shipped from the factory.

Change the setting as necessary.

Alarm Priorities: HI_HI_PRI, HI_PRI, LO_PRI,

and LO_LO_PRI

These parameters determine the respective

priority levels of the four types of process

alarms: HI_HI_ALM, HI_ALM, LO_ALM, and

LO_LO_ALM. Only the alarms whose priority

level is set to 3 or higher will be transmitted

upon occurrence.

These parameters are set to 1 before the

YTA320 is shipped from the factory.

Table 5.18

Alarm Priority

Value

Descriptions

0

Alart is not notified. Alarm parameters are

not updated.

1

Alart is not notified.

3 to 7

Advisory alarms.

8 to 15

Critical alarms.

Alarm Thresholds: HI_HI_LIM, HI_LIM,

LO_LIM, and LO_LO_LIM

These parameters determine the respective

thresholds for the four types of process alarms:

HI_HI_ALM, HI_ALM, LO_ALM, and LO_LO_

ALM. Before the YTA320 is shipped from the

factory, these parameters are set to values such

that no alarm will occur.

5.6.6 Parameters of DI Function Block

Parameters of function blocks can be read and

written from a host computer. See Appendix 1 for

a list of all parameters of the YTA320. This section

describes only the settings for important parameters

of each DI block.

MODE_BLK

Supports O/S, Auto, and Manual modes. The

DI block does not function in the O/S mode,

does not update the measured value in the

Manual mode, and updates the measured

value in the Auto mode. Normally, set the mode

to Auto. Before the YTA320 is shipped from the

factory, all the DI blocks are set to O/S mode.

CHANNEL

Selects the input to the DI block from the

transducer. The table below shows the input

value depending on the setting of CHANNEL.

Set CHANNEL according to the value you want

to input to the DI block.

Table 5.19

Input Selected by CHANNEL Setting

CHANNEL Setting

Input Selected

7

Limit switch 1

8

Limit switch 2

9

Limit switch 3

10

Limit switch 4

PV_FTIME

Stipulates the delay time (in seconds) of

changing the output value after a change of the

value inside the DI block.

DISC_PRI

Determines the priority level of the discrete

alarm on the block’s output (OUT_D). The

alarm will be transmitted upon occurrence only

when the DISC_PRI is set at 3 or higher. This

parameter is set to 1 before the YTA320 is

shipped from the factory.

Table 5.20

Alarm Priority

Value

Descriptions

0

Alart is not notified. Alarm parameters are

not updated.

1

Alart is not notified.

3 to 7

Advisory alarms.

8 to 15

Critical alarms.

DISC_LIM

Setpoint of the discrete alarm; when the value

of OUT_D agrees with the value set in DISC_

LIM, the discrete alarm is generated.

5.6.7 A setting when Sensor input 2 is not

connected

When Sensor input 2 is not connected, set

parameters as below.

SENSOR_TYPE_2 (Transducer Block)

Select “Non Connection”.

LIMSW_1(2 to 4)_TARGET (Transducer

Block)

Select “PRIMARY_VALUE_1” or

“SECONDARY_VALUE”.

CHANNEL (AI1 to AI4 function Block)

Set “1” or “3”. “1” means PRIMARY_VALUE_1

and “3” means SECONDARY_VALUE.