<8. Handling Caution>

8-10

IM 01C50T02-01E

*4:

Associated Nonincendive Field Wiring Apparatus

manufacturer’s installation drawing must be followed

when installing this equipment.

*5:

No revision to drawing without prior FM Approvals.

*6:

Terminator and supply unit must be FM Approved.

*7:

If use ordinary wirings, the general purpose equipment

must have nonincendive field wiring terminal approved by

FM Approvals.

*8:

The nonincendive field wiring circuit concept allows

interconection of nonincendive field wiring apparatus with

associated nonincendive field wiring apparatus, using any

of the wiring methods permitted for unclassified locations.

*9:

Installation requirements;

Vmax ≥ Voc or Vt

Imax = see note 10

Ca ≥ Ci + Ccable

La ≥ Li + Lcable

*10: For this current controlled circuit, the parameter (Imax) is

not required and need not be aligned with parameter (Isc

or It) of the barrier or associated nonincendive field wiring

apparatus.

Electrical Data:
• Supply Input (+ and –)

Maximum Input Voltage Vmax: 32 V

Maximum Internal Capacitance Ci: 1.5 nF

Maximum Internal Inductance Li: 8 µH

• Sensor Output (1 to 5)

Maximum Output Voltage Voc: 6.7 V

Maximum External Capacitance Co: 1.6 µF

Maximum External Inductance Lo: 7.2 mH

8.1.4 IECEx Certification

A) IECEx Flameproof Type and Dust Ignition

Proof Type

Caution for IECEx flameproof type and Dust Ignition

Proof Type

Note 1. Model YTA320/SF2 temperature

transmitters are applicable for use in

hazardous locations:

* No. IECEx KEM 07.0044

* Applicable Standard: IEC 60079-0:2004,

IEC 60079-1:2007-4, IEC 61241-0:2004,

IEC 61241-1:2004

* Type of Protection and Marking Code:

Ex d IIC T6/T5, Ex tD A21 IP67 T70°C,

T90°C

* Ambient Temperature for Gas

Atmospheres:

–40 to 75°C (T6), –40 to 80°C (T5)

* Ambient Temperature for Dust

Atmospheres:

–40 to 65°C (T70°C), –40 to 80°C (T90°C)

* Enclosure: IP67

Note 2. Electrical Data

* Supply voltage: 42 V dc max.

* Output signal: 4 to 20 mA

Note 3. Installation

* All wiring shall comply with local

installation requirement.

B) IECEx Intrinsically Safe type / type n
Caution for IECEx Intrinsically Safe and type n.

Note 1. Mode YTA320 temperature transmitter with

optional code /SS25 are applicable for use

in hazardous locations.

* No. IECEx CSA 05.0014

* Applicable Standards: IEC 60079-0:2000,

IEC 60079-11:1999, IEC 60079-15:2001

* Ex ia IIB/IIC T4, Ex nL IIC T4;

* Ambient Temperature: –40 to 60°C

* Enclosure: IP66 and IP67

Note 2. Electrical Data

* Intrinsic Safety Electrical Parameters

Ex ia IIC[Entity]: Ui=24 V, Ii=250 mA,

Pi=1.2 W, Ci=1.5 nF, Li=8 µH

Ex ia IIC[FISCO]: Ui=17.5 V, Ii=360 mA,

Pi=2.52 W, Ci=1.5 nF, Li=8 µH

Ex ia IIB[FISCO]: Ui=17.5 V, Ii=380 mA,

Pi=5.32 W, Ci=1.5 nF, Li=8 µH

Sensor Output: Uo=7.7 V, Io=70 mA,

Po=140 mW, Co=1.6 µF, Lo=7.2 mH

* Type “n” Electrical Parameters

Ex nL IIC: Ui=32 V, Ci=1.5 nF, Li=8 µH

Sensor Output: Uo=7.7 V, Io=70 mA,

Po=140 mW, Co=1.6 µF, Lo=7.2 mH

Model YTA320 Temperature transmitter with

optional code /SS25 can be selected the type of

protection (IECEx Intrinsically Safe or type n) for

use in hazardous locations.

Note 1. For the installation of this transmitter, once

a particular type of protection is selected,

another type of protection cannot be used.

The installation must be in accordance with

the description about the type of protection

in this instruction manual.

Note 2. In order to avoid confusion, unnecessary

marking is crossed out on the label other

than the selected type of protection when

the transmitter is installed.