<Appendix 4. PID Block>

A4-2

IM 01C50T02-01E

A4.3 Parameters of PID Block

NOTE: In the table below, the Write column shows the modes in which the respective parameters can be

written. A blank in the Write column indicates that the corresponding parameter can be written in all

modes of the PID block. A dash (-) indicates that the corresponding parameter cannot be written in any

mode.

Index Parameter Name

Default

(factory setting)

Write

Valid Range

Description

0

Block Header

TAG: “PID”

Block Tag =

O/S

Same as that for an AI block.

1

ST_REV

Same as that for an AI block.

2

TAG_DESC

(blank)

Same as that for an AI block.

3

STRATEGY

1

Same as that for an AI block.

4

ALERT_KEY

1

1 to 255

Same as that for an AI block.

5

MODE_BLK

6

BLOCK_ERR

Same as that for an AI block.

7

PV

Measured value; the non-dimensional value

that is converted from the input (IN) value

based on the PV_SCALE values and filtered.

8

SP

0

AUTO

PV_SCALE

±10%

Setpoint

9

OUT

MAN

Output

10

PV_SCALE

100

0

1133

1

O/S

Upper and lower scale limit values used for

scaling of the input (IN) value.

11

OUT_SCALE

100

0

1342

1

O/S

Upper and lower scale limit values used for

scaling of the control output (OUT) value to the

values in the engineering unit.

12

GRANT_DENY

0

AUTO

Same as that for an AI block.

13

CONTROL_OPTS

0

O/S

Setting for control action. See Section A4.13

for details.

14

STATUS_OPTS

0

O/S

See Section A4.15 for details.

15

IN

0

Controlled-value input

16

PV_FTIME

2

AUTO

Non-negative Time constant (in seconds) of the first-order

lag filter applied to IN

17

BYPASS

1 (off)

MAN

1, 2

Whether to bypass the control computation.

1 (off): Do not bypass.

2 (on): Bypass.

18

CAS_IN

0

Cascade setpoint

19

SP_RATE_DN

+INF

Positive

Rate-of-decrease limit for setpoint (SP)

20

SP_RATE_UP

-INF

Positive

Rate-of-increase limit for setpoint (SP)

21

SP_HI_LIM

100

PV_SCALE

±10%

Upper limit for setpoint (SP)

22

SP_LO_LIM

0

PV_SCALE

±10%

Lower limit for setpoint (SP)

23

GAIN

1

Proportional gain (= 100 / proportional band)

24

RESET

10

Integration time (seconds)

25

BAL_TIME

0

Positive

Unused

26

RATE

0

Positive

Derivative time (seconds)

27

BKCAL_IN

0

Read-back of control output

28

OUT_HI_LIM

100

OUT_SCALE

±10%

Upper limit for control output (OUT)

29

OUT_LO_LIM

0

OUT_SCALE

±10%

Lower limit for control output (OUT)

30

BKCAL_HYS

0.5 (%)

0 to 50%

Hysteresis for release from a limit for OUT.

status

31

BKCAL_OUT

0

Read-back value to be sent to the BKCAL_IN

in the upper block