Yokogawa 415 Steam and Gas User Manual

Page 38

Advertising
background image

Example

A flowmeter has been tested and the following relationship between
the input and the flowrate has been determined at the nominal
temperature & pressure as follows:

Input

Flowrate

Normalised Inputs for

table

Inches

wg

D.P. Output

mA

lbs/hr

Input (A) Output (A

C

)

52.2007 20.000 7075.89 1.0000 1.0000

39.3894 5306.92

0.7546

0.7500

33.3231 4422.43

0.6384

0.6250

26.7444 3537.94

0.5123

0.5000

20.1656 2653.45

0.3863

0.3750

12.9913 1768.97

0.2489

0.2500

5.5400 884.48

0.1061

0.1250

1.0388 269.06

0.0199

0.0380

0.0000 4.0000

0

0.0000 0.0000

where

A =

Inches wg

Inches wg at 20mA

=

Inches wg

52.2007

A

C

=

flowrate

flowrate at 20mA

=

flowrate

7075.85

The values of A and A

C

are input into the table during Calibration

and the span would be programmed as 7075.89 such that

Q = 7075.89 x A

C

36 Operation