App index prntouts (pen model) – Yokogawa µR20000 User Manual

Page 233

Advertising
background image

12-5

IM 04P02B01-01E

Spec

fcat
ons

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

Prntouts (Pen Model)

Item

Specfcatons

Recording pen (color)

Plotter pen (purple)

Alarm printout

Prints alarm occurrence/release.

Printout contents

Occurrence ( )/release ( ) marks, channel number or tag, alarm type, alarm level, time, printout

buffer overflow mark.

Time printout format

Selectable from hour:minute, hour:minute:second, month:day:hour:minute, month:day:hour:minute:

second, and year:month:day:hour:minute:second.

Alarm printout buffer

Stores 24 occurrences of alarm information waiting to be printed.

Periodic printout

Prints at specified time intervals from the reference time.

Interval

Reference time: 00 hour 00 minute to 23 hour 00 minute (1 hour steps, minute fixed)

(see appendix 2)

Auto:

Automatically determined from the chart speed.

Manual:

Select 10 min, 12 min, 15 min, 20 min, 30 min, 1 hour, 2 hours, 3 hours, 4 hours,

6 hours, 8 hours, 12 hours, or 24 hours.

Mode

Selectable from disable periodic printout, print instantaneous values, and print report data (report mode).
Report data: Selectable from the average, minimum, maximum, minimum/maximum/average, sum

value, and instantaneous value.

Printout contents

For instantaneous values: Date/Time, offset compensation ON/OFF, channel information (measured

value, alarm status, unit, delta computation ON/OFF, scale, channel

number or tag, recording color), chart speed (with time ticks)

For report data: Report start/end date/time, offset compensation ON/OFF, events, channel

information (value, unit, range change occurrence, scale, recording color), chart

speed (with time ticks)

Message printout

Prints preset message strings.

Number of messages

5

Printout contents

Time, message (up to 16 characters), printout buffer overflow mark.

Time printout format

Selectable from hour:minute, hour:minute:second, month:day:hour:minute,

month:day:hour:minute:second, year:month:day:hour:minute:second, and not print.

Message printout buffer Stores 5 messages waiting to be printed.

Recording start printout

Prints at the start of recording.

Printout contents

Time and chart speed, printout buffer overflow mark.

Time printout format

Selectable from hour:minute, hour:minute:second, month:day:hour:minute,

month:day:hour:minute:second, and year:month:day:hour:minute:second.

New chart speed printout Prints when the chart speed is changed.

Printout contents

Chart speed and time, printout buffer overflow mark.

Time printout format

Selectable from hour:minute, hour:minute:second, month:day:hour:minute,

month:day:hour:minute:second, and year:month:day:hour:minute:second.

Manual printout

Prints the measured values of all channels.

Printout contents

Measured values of all channels at that point.
Trend recording is temporarily suspended.

Setting printout (List)

Prints the settings of items in Setting mode.

Printout contents

Range setting, alarm setting, etc.
Trend recording is temporarily suspended.

Setting printout (Setup)

Prints the settings of items in Basic Setting mode.

Printout contents

Basic alarm specifications, basic recording specifications, etc.
Trend recording is temporarily suspended.

Items dependent on the

chart speed

Chart speed

Perodc prntout

Alarm prntout

Message prntout

Record start prntout

New chart speed prntout

5 to 9 mm/h

Not printed

Printed

10 to 1500 mm/h

Printed

Printed

1600 mm/h or higher

Not printed

Not printed

Chart speed

Perodc prntout nterval

10 to 18 mm/h

8 hours

20 to 36 mm/h

4 hours

40 to 72 mm/h

2 hours

75 to 135 mm/h

1 hour

150 to 180 mm/h

30 minutes

200 to 320 mm/h

20 minutes

350 to 1500 mm/h

10 minutes

Date printout format

Select the printout format of the date from Y/M/D, M/D/Y, D/M/Y, D.M.Y, and M.D.Y. The format

applies to the date printout of all printout items.

12.3 Recordng Functon Specfcatons

Advertising