V. start up – Sterling ME User Manual

Page 14

Advertising
background image

— 14 —

5. After approximately 15 minutes of unit operation,

determine volume of gas used in fi ve minutes of unit
operation. For the Example above the unit should use
4.17 ft

3

/min x 5 minor 20.8 ft

3

(1.97 L/s x 5 min x 60 s/

min = 591L) of gas. Minor input adjustments can be
made by removing pressure regulator cap and turning
regulator clockwise to increase input or counter
clockwise to decrease input. Any appreciable
adjustment in input rate should be made by reorifi cing.

Method to Check Manifold Pressure
1. Close the manual valve of unit gas valve.

2. Install a

1

/

8

" pipe connection in the tapped hole

provided in the gas valve body near outlet of the valve.

3. Attach manometer to

1

/

8

" pipe connection by means

of a rubber hose.

4. Fire unit according to instructions and observe the

pressure and confi rm it matches the unit manifold
pressure from the unit rating plate.

5. Small variations in the manifold pressure can be

made by means of the gas valve pressure regulator.
Remove pressure regulator cap and turn regulator
clockwise to increase pressure or counter-clockwise
to decrease pressure.

PILOT ADJUSTMENT
1. Disconnect wire from terminal marked MV at gas valve.

2. Provide call for heat.

3. Pilot adjustment is found on the gas valve. Remove

pilot adjustment cap.

4. Adjust the pilot screw to provide properly sized fl ame.

5. A proper pilot burner fl ame is a soft steady fl ame that

envelopes

3

/

8

to

1

/

2

inch (9.5 to 12.7mm) of the fl ame

sense probe tip.

6. Replace the pilot adjustment cap.

7. Reconnect wire to terminal MV.

PRIMARY AIR SHUTTER ADJUSTMENT
After the unit has been in operation for at least 15
minutes, adjust the primary air fl ow to the burners. Turn
the friction-locked manually rotated air shutters clockwise
to close, counter clockwise to open. For correct air
adjustment, close the air shutter until yellow tips in the
fl ame appear. Then open the air shutter to the point just
beyond the position where yellow tipping disappears.

CONTROLS
(also see the Indoor Duct Furnace Manual):
Primary Limit Control:
The primary limit control is a
factory installed component surface mounted in the inlet
airstream at the end of the heat exchanger. When the
temperature reaches the limit setpoint, normally caused
by insuffi cient air throughput, all gas is shutoff. The limit
control has an automatic reset and once the unit has
cooled, it will reset itself. This is a safety control and if
cycling on the primary limit is noted, corrective action must
be taken. See unit wiring diagram for electrical location.
This control must never be bypassed. Upon completion of
unit installation, the primary limit must be checked for
proper operation. This can be accomplished by removing
power to the indoor air blower and a call for heat.

Clogged Filter Switch: (Optional) The clogged fi lter switch
monitors the pressure differential across the air fi lters. If
this pressure differential becomes too great, the switch will
alert of this condition. At this point the air fi lters must either
be cleaned or replaced. The switch will reset itself.

Firestat: (Optional) Located in either the return
airstream, the supply airstream, or both, this control
monitors temperatures with setpoints which are fi eld
adjustable. If the temperature exceeds the setpoint, the
control will cease unit operation. To resume unit
operation, a manual reset of this control is required.

Freezestat: (Optional) Located in either the return
airstream, the supply airstream, or both, this control
monitors temperatures with setpoints which are fi eld
adjustable. If the temperature does not exceed the
setpoint, the control will cease unit operation.

V. START UP

Before starting the unit, use the “Installation Check
Sheet” (located at the end of this manual) and read the
Indoor Duct Furnace Manual entirely in conjunction with
the procedures outlined below to ensure that the unit is
completely and properly installed and ready for start up.

It is the installer’s responsibility to

check all safety controls! Check and test the
operational functions of all safety devices
supplied with this unit. Failure to do so could
result in unsafe conditions and may result in
death, serious injury or property damage.

1. Inspect all wiring connections; connections should be

clean and tight. Trace circuits to insure that actual
wiring agrees with the “as wired” diagrams
provided with the unit.
Information in the wiring
diagram title block should match the data appearing
on the unit nameplate.

2. Lubricate all electrical motors according to the

manufacturer’s recommendations.