Troubleshooting guide dx cooling coil – Sterling ME User Manual

Page 23

Advertising
background image

— 23 —

PROBLEM

PROBABLE CAUSE

SOLUTION

6. Belts mismatched

Belts improperly tensioned, causing

Replace belts and tension drive with slack of each

after service

more stretch of some belts than others. belt on the same side of the drive.

Old belts and new belts used

Replace with new belts.

on same drive.

Different brand name belts used

Replace with a set of Machine Matched Belts.

on same drive.

Driver and driven shafts shifted

Realign drive.

from parallel.

Belt cord section damaged during

Replace belts and install properly.

installation.

7. Drive fails to adjust

Fretting corrosion (drive allowed to

Driver pulley must be disassembled,

operate at one speed over a period

cleaned and lubricated, then

of time).

reassembled.

TROUBLESHOOTING GUIDE

DX COOLING COIL

PROBLEM

PROBABLE CAUSE

SOLUTION

1. No or Insuffi cient

Coil icing.

a. Low liquid line pressure.*

Cooling

b. Thermal expansion valve.**

c. Low air fl ow across coil.

Air binding.

Purge and charge system.

Thermal expansion valve.**

a. Bulb mounted at incorrect location.

b. Bulb not secured properly.

Insuffi cient air fl ow.

a. See air blower troubleshooting.

b.

Clogged

coil

Air bypassing coil.

Caulk safe off.

Undersized system, demand

Replace system.*

exceeding cooling system capacity.

Too much outside air.

Check outside air dampers.

Refrigerant leak.

Determine leak location and correct.

Low liquid pressure.

Determine cause and correct.*

2. Water in Conditioned Air Exceeding coil face velocity - 600 fpm. Reduce unit air fl ow.

Drain pan p-trap clogged.

Clean pan and p-trap.

* Refer to condensing unit installation and service manual.
**Refer to thermal expansion valve installation instruction.