Maintenance schedule – MAHLE RTI CSC10 User Manual

Page 13

Advertising
background image

- 12 -

3. Add 4 fluid ounces of Automotive Reinhibitor For CSC10R for each gallon of processed coolant.

Mix well, by placing hose from hand pump into small opening on drum and recirculating.

4. After adding the initial amount of reinhibitor, measure the pH of the processed coolant using the pH

Dip Sticks (supplied) or a pH meter. The desired pH is between 9.2 and 10.6.

5. If the measured pH is below this range, add additional 1 fluid ounce of reinhibitor per gallon of

processed coolant and mix well. Repeat this step until the pH is within the target range OR until a
TOTAL of 8 fluid ounces of reinhibitor has been added for each gallon of processed coolant. Only
add as much inhibitor as needed.

The recycled coolant is now ready for use!

Maintenance Schedule

EVERY USE:

CLEAN ANY SPILLS - Antifreeze/coolants and reinhibitor can be corrosive to the unit's painted finish.
Thoroughly wipe, rinse and dry any spills immediately.

WEEKLY:

FLUSH EVACUATION PUMP - Fill a bucket with cool, clean water. Insert the Plastic Wand on the
RED Suction Hose into the bucket. Turn ON the Evacuation Pump (located on the front bevel of the
unit). Turn OFF the Evacuation Pump when the bucket is empty.

CHANGE AS REQUIRED:

REPLACE FILTERS - If the filtering process
takes more than 10 minute or stops completely, the
filters require changing.

1. Disconnect the power cord.

2. Unscrew the filter housing. Remove used

cartridge and discard properly.

3. Rinse the filter housing with water and dry.

Remove the O-ring from the housing and wipe
groove and O-ring clean.

4. Lubricate the O-ring with a coating of clean petroleum jelly.

5. Place the O-ring back in place, pressing it down into the groove with two fingers.