STI HK3 User Manual

Page 2

Advertising
background image

2

Warnings and Installation Notes

1.

Use of an outdoor rated initiating station is required with this heated enclosure.

2.

When conducting periodic testing, if conditions are dusty or if you have wind blown dust conditions, cover return grill ports to
minimize entrance of dust or sand particles. To remove accumulated dust or sand particles, use small containers of compressed
air that is used for electronic cleaning.

3.

To reset the thermal circuit breaker push button.
If circuit breaker will not remain in a restored or closed position, conduct an electrical check of the various components in the
two voltage classes. The two voltage classes are 24 VDC Negative Ground and 110 or 240 VAC 50-60 Hz with connected elec-
trical or earth ground. High voltage (110 or 240 VAC) wiring must enter through bottom conduit. Low voltage and signaling wires
must enter through top conduit and remain separated per NFPA 70, NEC, and local codes.

4.

If the thermal circuit breaker has tripped (opened circuit), the 110 or 240 VAC 50-60 Hz power will still be energized up to the
primary side of the thermal breaker. For safety, disconnect supply power of conductors to three power circuits in the enclosure.

5.

To clean 24 VDC negative ground fan with electronic compressed air container, disconnect all power.
Note: the 24 VDC negative ground fan will not operate if positive and negative conductors are connected on the wrong termi-
nals.

6.

To minimize arid summer time heat build up in enclosure, install a dark color sun shield with sides to provide shade for the
enclosure. At the inclined face above the enclosure at the point of contact with the building structure leave at least 1/2” or (1.25
cm) space. This will generate heat and cause an upward airflow and help maintain the enclosure temperature approximately
the same as ambient air temperature.

7.

The 110 or 240 VAC single phase 50-60 Hz heater does not require standby or secondary power because the enclosure envi-
ronment is supervised by a latching supervisory circuit in the alarm control unit or panel.

8.

Replacement of heater assembly and gasket is required five years from installation date. Contact STI to order replacement
Heater Kit STI-HK3.

9.

All field wiring within this enclosure must be rated for a minimum operating range of 0ºC - 110ºC.

The enclosure is used to protect UL Listed 38 and 2017 initiating devices at temperatures down to -70˚F (-57˚C). It is the
installer’s responsibility to comply with NEC 70 Articles 725 and 760, NFPA 72, and other applicable fire and electrical codes.
Conduit or raceway paths need to be sealed as near to the enclosure as possible. Installer should have maintained supervision
over the low temperature thermostat. The low temperature monitoring thermostat makes the circuit at +32°F (0°C) and clears
the circuit at +50°F (+10°C). This listing requires that the fire alarm supervisory control module be only of the latching type. On
the appliance mounting plate is a label where you should record the installation date. Also include below the serial number and
installation date on the instruction sheet for quick reference.

Serial Number__________________________________ Installation Date__________________
NOTE: Operating voltage for the STI-1200A-HTR is 110 VAC. Operating voltage for the STI-1200A-HTR240 is 240 VAC.

1.

Use of an outdoor rated initiating station is required with this heated enclosure.

2.

When conducting periodic testing, if conditions are dusty or if you have wind blown dust conditions, cover return grill ports to minimize entrance
of dust or sand particles. To remove accumulated dust or sand particles, use small containers of compressed air that is used for electronic clean-
ing.

3.

To reset the thermal circuit breaker push button.
If circuit breaker will not remain in a restored or closed position, conduct an electrical check of the various components in the two voltage class-
es. The two voltage classes are 24 VDC Negative Ground and 110 or 240 VAC 50-60 Hz with connected electrical or earth ground. High voltage
(110 or 240 VAC) wiring must enter through bottom conduit. Low voltage and signaling wires must enter through top conduit and remain sepa-
rated per NFPA 70, NEC, and local codes.

4.

If the thermal circuit breaker has tripped (opened circuit), the 110 or 240 VAC 50-60 Hz power will still be energized up to the primary side of the
thermal breaker. For safety, disconnect supply power of conductors to three power circuits in the enclosure.

5.

To clean 24 VDC negative ground fan with electronic compressed air container, disconnect all power.
Note: the 24 VDC negative ground fan will not operate if positive and negative conductors are connected on the wrong terminals.

6.

To minimize arid summer time heat build up in enclosure, install a dark color sun shield with sides to provide shade for the enclosure. At the
inclined face above the enclosure at the point of contact with the building structure leave at least 1/2” or (1.25 cm) space. This will generate heat
and cause an upward airflow and help maintain the enclosure temperature approximately the same as ambient air temperature.

7.

The 110 or 240 VAC single phase 50-60 Hz heater does not require standby or secondary power because the enclosure environment is super-
vised by a latching supervisory circuit in the alarm control unit or panel.

8.

Replacement of heater assembly and gasket is required five years from installation date. Contact STI to order replacement Heater Kit STI-HK3.

9.

All field wiring within this enclosure must be rated for a minimum operating range of 0ºC - 110ºC.

Le boîtier est utilisé pour protéger les dispositifs de déclenchement homologués UL 38 et 2017 à des températures allant jusqu’à -70 °F (-57 °C).
Il incombe à l’installateur de se conformer aux articles 725 et 760 de la NEC 70, NFPA 72, et aux autres codes de prévention des incendies et de
l’électricité en vigueur. Les chemins des conduites ou canalisations doivent être scellés aussi proche que possible du boîtier. Il est attendu que
l’installateur ait effectivement contrôlé le thermostat à basse température. Le contrôle du thermostat à basse température maintient le circuit à 32
°F (0 °C) et déclenche le circuit à 50 °F (10 °C). Cette homologation exige nécessite que le module de contrôle de la surveillance des alertes
d’incendie soit uniquement du type à verrouillage. La plaque de montage de l’appareil comporte une étiquette sur laquelle vous devez enregistrer
sa date d’installation. Le numéro de série et la date d’installation doivent aussi être marqués sur la feuille d’instruction pour référence rapide.

Numéro de série ____________________ Date d’installation ______________

REMARQUE: La tension de service du STI-1200A-HTR est de 110 VCA. La tension de service du STI-1200A-HTR240 est de 240 VCA.

Mises en garde et remarques sur l’installation

Advertising
This manual is related to the following products: