Installation Instructions

Mount Enclosure back box - Refer to Fig 1

1. Set heater assembly with cover aside. Press (4) plastic tabs into slots on back box and drill (4)

1/4” (6.4mm) diameter holes in mounting surface for plastic anchors provided. Attach back
box to wall using (4) #10 x 1-1/2”screws provided.

2. Attach 3/4” rigid conduit and conduit sealing hub (Crouse-Hinds 3/4” EYSX 21 or equivalent)

to back box. Conduit should be installed according to applicable NEC and local codes.

3. Pull 24 VDC and alarm wiring into back box through top conduit; and pull 110 or 240 VAC

wiring into back box through bottom conduit per NFPA 70, NEC and local codes.
Note: Wire size to be 12-22 AWG.
Install Fire Alarm Pull Station and Dual Monitor Module to Heater and Cover
Assembly - Refer to Fig 2.

4. Lift the cover from heater assembly and allow it to hang from cables. Connect the provided

high temperature wires to the pull station.

5. Attach the pull station to the slide plate using (2) #6-32 x 3/8” screws provided. Adjust the

slide plate so the pull station or slide plate does not cover either the fan opening or vent slots.
Note: If the fan opening or vent slots are covered, the plate mounting screws can be moved
to the alternate mounting position. After mounting pull station adjust the slide plate so there
are no gaps large enough to touch the heaters behind the pull station.

0

8 7

/1

6 i

n.

(21

4m

m)

4 3

/8

in

.

(11

1m

m)

LOW VOLTAGE

WIRE INPUT

SEALING HUB
(NOT PROVIDED)

3/4 in. NPT MALE NIPPLE

(NOT PROVIDED)

MOUNTING TAB
(4) PROVIDED

BACKBOX

#10 x 1 1/2 in.

PAN HEAD SCREW
(4) PROVIDED

HIGH VOLTAGE WIRE INPUT

MOUNTING

SURFACE

SCREW ANCHORS

(4) PROVIDED

DRILL (4) 1/4 in. (6.4mm)

DIAMETER HOLES

3/4 in. NPT MALE

NIPPLE (NOT PROVIDED)

SEALING HUB

(NOT PROVIDED)

FIG. 1