5. Use the wire tightening screws to secure the wires.

6. Insert the DC power supply wiring assembly with the wires connected into the power supply

and tighten the assembly screws. Refer to

Figure 17

.

7. Using the handle on the power supply, hold the power supply level and guide it into the carrier

rails on each side of the power supply slot. Gently push the power supply all the way into the
slot, ensuring that it firmly engages with the connector.

8. When you are sure the power supply has properly engaged the connector, tighten the chassis

attachment screws to secure the power supply in the slot.

When the Brocade ICX 7750 is powered on, the power LED on the front of the device should turn
green to confirm that the power supply is correctly installed and supplying power. Refer to the
section

“Brocade ICX 7750 front panel LEDs”

on page 25.

DC-DC power source cautions

A caution calls your attention to a possible hazard that can damage equipment.

"Vorsicht" weist auf eine mögliche Beschädigung des Geräts hin. Sie finden die folgenden
Vorsichtshinweise in diesem Handbuch.

Une mise en garde attire votre attention sur un risque possible d'endommagement de
l'équipement. Ci-dessous, vous trouverez les mises en garde utilisées dans ce manuel.

Un mensaje de precaución le advierte sobre un posible peligro que pueda dañar el equipo. Las
siguientes son precauciones utilizadas en este manual.

CAUTION

For DC system, use grounding wire of at least 12 American Wire Gauge (AWG). The grounding
wire should be attached to the DC input connector (as shown in

Figure 17

); the other end

connects to the building ground.

VORSICHT

Für Gleichstromsystem verwenden Erdungskabel von mindestens 12AWG (3.31 mm2)
(amerikanische Norm für Drahtquerschnitte). Der Erdungsdraht sollte DC-Eingang angeschlossen
werden (wie in

Figure 17

zeigen #14), das andere Ende verbindet sich mit dem Baugrund.

MISE EN GARDE

ATTENTION: Pour les systèmes d'alimentation courant continu (C.C), utilisez un fil de mise à terre
d'au moins de 12 AWG (ou 3.31mm2). Le fil de mise à terre doit être relié au connecteur du
circuit d'alimentation (voir

Figure 17

); l'autre extrémité se connecte à la prise terre du batiment.

CAUTION

For the DC input circuit to the system, make sure there is a 20 Amp circuit breaker, minimum 60
VDC, double pole, on the input terminal block to the power supply. The input wiring for connection
to the product should be copper wire, 12 AWG, marked VW-1, and rated minimum 90°C.